Plan Review Notes For Permit 01111005 |
Permit Number |
01111005 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-02-13 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) SHT A-02 RISER DIAGRAM DOES NOT RE- | | FLECT FLOOR PLAN. W/M ON FLOOR PLAN IS | | AFTER RISER FOR 2ND FLOOR AND NO VENT IS | | SHOWN ON FLOOR PLAN. RISER DIAGRAM SHOWS | | W/M BEFORE RISER FOR 2ND FLOOR AND RE- | | VENT BELOW FLOOR LEVEL NOT ALLOWED. SEC | | 906.3 SEE COMMENTS 3'S ONE AND TWO FROM | | PREVIOUS REVIEW. | | 2) SHT A-02 FLOOR PLAN DOES NOT SHOW | | SEPARATE STACK FOR M/BATH AS SHOWN ON | | RISER. SEE COMMENT #7 FROM PREVIOUS RE- | | VIEW. | | 3) SHT A-02 FLOOR PLAN SHOWS 2" VTR FOR | | POWDER ROOM & 3" VTR ON RISER DIAGRAM. | | PLEASE CLAIRFY. | | 4) SHT A-02 RUNNING TRAP AT M/BATH TUB | | NOT APPROVED AS SHOWN ON RISER DIAGRAM. | | SEE COMMENT #8 FROM PREVIOUS REVIEW. | | 5) SHT A-02 LAVS IN M/BATH AND BATH #2 | | ARE "S" TRAPPED ON RISER DIAGRAM. THESE | | TRAPS ARE NOT APPROVED. SEC 1001.5.2 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|