Plan Review Notes
Plan Review Notes For Permit 01111005
Permit Number 01111005
Review Stop P
Sequence Number 2
Notes
Date Text
2002-02-13 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT A-02 RISER DIAGRAM DOES NOT RE-
 FLECT FLOOR PLAN. W/M ON FLOOR PLAN IS
 AFTER RISER FOR 2ND FLOOR AND NO VENT IS
 SHOWN ON FLOOR PLAN. RISER DIAGRAM SHOWS
 W/M BEFORE RISER FOR 2ND FLOOR AND RE-
 VENT BELOW FLOOR LEVEL NOT ALLOWED. SEC
 906.3 SEE COMMENTS 3'S ONE AND TWO FROM
 PREVIOUS REVIEW.
 2) SHT A-02 FLOOR PLAN DOES NOT SHOW
 SEPARATE STACK FOR M/BATH AS SHOWN ON
 RISER. SEE COMMENT #7 FROM PREVIOUS RE-
 VIEW.
 3) SHT A-02 FLOOR PLAN SHOWS 2" VTR FOR
 POWDER ROOM & 3" VTR ON RISER DIAGRAM.
 PLEASE CLAIRFY.
 4) SHT A-02 RUNNING TRAP AT M/BATH TUB
 NOT APPROVED AS SHOWN ON RISER DIAGRAM.
 SEE COMMENT #8 FROM PREVIOUS REVIEW.
 5) SHT A-02 LAVS IN M/BATH AND BATH #2
 ARE "S" TRAPPED ON RISER DIAGRAM. THESE
 TRAPS ARE NOT APPROVED. SEC 1001.5.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377