Plan Review Notes
Plan Review Notes For Permit 01111005
Permit Number 01111005
Review Stop E
Sequence Number 2
Notes
Date Text
2002-02-13 00:00:00****************** UNSAT ***************
  
 REVIEW FOR MODEL "C"
  
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED.
 PLEASE NOTE THAT OTHER CHANGES WERE
 MADE THAT NOW NEED TO BE ADDRESSED.
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 MISSING FIRST FLOOR.
  
 2) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING IN SOME LOCATIONS.
  
 3)NOTE: PLEASE NOTE MISSING REQ`D EGRESS
 LIGHTING AT MANY LOCATIONS. PER 210-70
  
 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 FOOTER STEEL.
  
 5) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
 6)NOTE: PLEASE NOTE THAT OUTLET SPACING
 ALONG KITCHEN COUNTERSPACES SEEM TO
 HAVE CHANGED WHEN "GFI" WAS ADDED?
 PLEASE CLARFIY "TWO" OUTLETS SHOWN
 TOGETHER. SHOWN ON OTHER MODELS LIKE
 THIS. 210-52-C1
  
 7)NOTE: PLEASE NOTE THAT NOTES ON RIGHT
 STILL REFERENCE ART FOR BATHS WHEN NOTED
 FOR KITCHEN? PLEASE CORRELATE. 210-11-C-
 1. NOTED AS 210-52D"BATHS".
  
 8)NOTE: PLEASE NOTE THAT DERATING FOR
 AHU WAS TAKEN TWICE AT 65%?? PLEASE
 CORRECT. 220
  
 9)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO MEET 220. PLEASE NOTE THAT LOAD
 IS SHOWN AS BEING DIVIDED BY 120V ON
 A 230/240V SERVICE? PLEASE CLARIFY.
  
 10)NOTE: PLEASE NOTE RISER DIAGRAM WAS
 REVISED AND NOW SHOWS AN EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN METER AND
 MAIN DISCONNECT? PLEASE NOTE THAT THIS
 IS PARALLELING THE NEUTRAL?
  
 11)NOTE: PLEASE NOTE MISSING HALL OUTLET
 UPSTAIRS PER 210-52H
  
 12)NOTE: PLEASE NOTE THAT RISER SHOWS
 3/0`S GOING TO A 30A POOL PANEL? PLEASE
 SHOW PANEL ON PLANS AND SHOW OCP AND
 CONDUCTOR SIZE FOR POOL PANEL ON MAIN
 PANEL SCHEDULE.
  
 13)NOTE: PLEASE NOTE MISSING REQ`D BATH
 GFI FOR POWDER ROOM FIRST FLLOR.210-52D
  
 14)NOTE: PLEASE NOTE THAT NO OUTLET IS
 SHOWING FOR RANGE. ALSO NOT SHOWN ON
 OTHER PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372