2002-02-13 00:00:00 | ****************** UNSAT *************** |
| |
| REVIEW FOR MODEL "C" |
| |
| PLEASE NOTE THAT NOT ALL NOTES FROM |
| FIRST REVIEW WERE ADDRESSED. |
| PLEASE NOTE THAT OTHER CHANGES WERE |
| MADE THAT NOW NEED TO BE ADDRESSED. |
| |
| 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| MISSING FIRST FLOOR. |
| |
| 2) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| MISSING IN SOME LOCATIONS. |
| |
| 3)NOTE: PLEASE NOTE MISSING REQ`D EGRESS |
| LIGHTING AT MANY LOCATIONS. PER 210-70 |
| |
| 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50. |
| FOOTER STEEL. |
| |
| 5) PLEASE NOTE MISSING OUTLET FOR A/C |
| EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| MECHANICAL CODE. |
| |
| 6)NOTE: PLEASE NOTE THAT OUTLET SPACING |
| ALONG KITCHEN COUNTERSPACES SEEM TO |
| HAVE CHANGED WHEN "GFI" WAS ADDED? |
| PLEASE CLARFIY "TWO" OUTLETS SHOWN |
| TOGETHER. SHOWN ON OTHER MODELS LIKE |
| THIS. 210-52-C1 |
| |
| 7)NOTE: PLEASE NOTE THAT NOTES ON RIGHT |
| STILL REFERENCE ART FOR BATHS WHEN NOTED |
| FOR KITCHEN? PLEASE CORRELATE. 210-11-C- |
| 1. NOTED AS 210-52D"BATHS". |
| |
| 8)NOTE: PLEASE NOTE THAT DERATING FOR |
| AHU WAS TAKEN TWICE AT 65%?? PLEASE |
| CORRECT. 220 |
| |
| 9)NOTE: PLEASE NOTE LOAD CALCULATIONS |
| NEED TO MEET 220. PLEASE NOTE THAT LOAD |
| IS SHOWN AS BEING DIVIDED BY 120V ON |
| A 230/240V SERVICE? PLEASE CLARIFY. |
| |
| 10)NOTE: PLEASE NOTE RISER DIAGRAM WAS |
| REVISED AND NOW SHOWS AN EQUIPMENT |
| GROUNDING CONDUCTOR BETWEEN METER AND |
| MAIN DISCONNECT? PLEASE NOTE THAT THIS |
| IS PARALLELING THE NEUTRAL? |
| |
| 11)NOTE: PLEASE NOTE MISSING HALL OUTLET |
| UPSTAIRS PER 210-52H |
| |
| 12)NOTE: PLEASE NOTE THAT RISER SHOWS |
| 3/0`S GOING TO A 30A POOL PANEL? PLEASE |
| SHOW PANEL ON PLANS AND SHOW OCP AND |
| CONDUCTOR SIZE FOR POOL PANEL ON MAIN |
| PANEL SCHEDULE. |
| |
| 13)NOTE: PLEASE NOTE MISSING REQ`D BATH |
| GFI FOR POWDER ROOM FIRST FLLOR.210-52D |
| |
| 14)NOTE: PLEASE NOTE THAT NO OUTLET IS |
| SHOWING FOR RANGE. ALSO NOT SHOWN ON |
| OTHER PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |