2002-01-15 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| SBC = STANDARD BUILDING CODE |
| SBC*= STANDARD BUILD'G CODE (AMENDMENTS) |
| |
| 1) SEE REVIEW, DATED 1/15/02, OF MODEL B |
| (PERMIT NO. 01111002) FOR GENERAL |
| COMMENTS.COMMENTS SPECIFIC TO MODEL C |
| ARE LISTED BELOW. |
| |
| 2) THE PAD FOOTINGS UNDER GARAGE WALL |
| COLUMNS AND THE PATIO COLUMN SHALL NOT |
| ENCROACH ON THE COMMON PROPERTY (ZERO |
| LOT) LINE. |
| |
| 3) SHEET A-02, FOUNDATION PLAN.THE |
| FOOTING SCHEDULE IS BLANK. ADD DETAILS. |
| |
| 4) SBC 705.1.3OPENING PROTECTIVES. |
| TABLE 600 REQUIRES THE SECOND FLOOR |
| BED 3 EXTERIOR WALL FACING TH COMMON |
| PROPERTY LINE TO HAVE A MINIMUM FIRE |
| RESISTANCE RATING OF ONE HOUR.SUBMIT |
| DETAILS TO SHOW THE RATING OF THIS WALL. |
| |
| 5) MODELS C, D AND E.THE DOOR SCHEDULE |
| IS MISSING ALL REFERENCE MARKS ABOVE |
| NO. 14.AMEND SCHEDULES. |
| |
| 6) SHEET A-06, BEAM SCEDULE,DOES NOT |
| GIVE DETAILS FOR THE BEAMS, REF 8F01B ON |
| SHEET A-07, TO THE STAIRCASE WINDOW AND |
| MASTER BEDROOM WALK-IN CLOSET WINDOW. |
| REVISE SCHEDULE TO SHOW BEAM TYPE & SIZE |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUERIES PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |