Plan Review Notes
Plan Review Notes For Permit 01111005
Permit Number 01111005
Review Stop P
Sequence Number 1
Notes
Date Text
2001-12-07 00:00:00DENIED
 REFERENCE: SPC-94-SBC-97
  
 1) SANITARY RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN. STACK FOR BATH #2 UPSTAIRS
 SHOULD BE TAKEN OFF BEFORE W/MACHINE.
 2) W/MACHINE NOT VENTED ON RISER DIAG.
 3) LAV IN POWDER ROOM NOT VENTED ON DIAG
 4) 3" STACK NOT ALLOWED IN BLOCK WALL &
 CAN NOT PASS THRU TIE BEAM. SBC-97 SEC
 1907.3.5
 5) TUB NOT VENTED IN BATH #2, SPC SEC
 913.2
 6) DISH WASHER DRAIN SHALL GO TO GARBAGE
 DISPOSAL OR TAILPIECE ON KITCHEN SINK.
 7) DISCHARGE FROM MASTER BATH SHALL NOT
 DRAIN INTO VENT STACK FOR KITCHEN SINK.
 SPC SEC 913.2 & 910.2. SEPARATE VENT RE-
 QUIRED FOR KITCHEN SINK.
 8) RUNNING TRAPS IN MASTER BATH TUB NOT
 ALLOWED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377