Date Text
2002-03-13 00:00:00************** UNSAT *****************
  
 MODEL "B"
  
 1) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 STILL MISSING FROM ATRIUM TO OUTSIDE.??
  
 2)NOTE: PLEASE NOTE THAT A POOL DISC
 AND POOL PANEL ARE BOTH SHOWN ON THE
 RISER DIAGRAM? PLEASE NOTE THAT POOL
 PANEL IS STILL NOT SHOWN ON POOL PANEL.,
 POOL PANEL IS BEING SHOWN IN GARAGE AND
 THE POOL PANEL DISC IS SHOWN AT THE
 REAR OF HOUSE?? PLEASE CORRELATE
 LOCATIONS.
  
 3)NOTE: PLEASE NOTE THAT POOL PANEL IS
 BEING FED WITHTWO "HOTS"? PLEASE
 CLARIFY WHERE NEUTRAL AND EQUIPMENT
 GROUNDING CONDUCTOR,
  
 4)NOTE: PLEASE NOTE THAT LOAD CALCULATIO
 NS NEED TO BE GONE OVER AND DONE PER
 NEC(220),
 PLEASE NOTE, 40% DERATING SEEMS TO BE
 TOO LOW. PLEASE RECONFIGURE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW