Plan Review Notes For Permit 01111002 |
Permit Number |
01111002 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-03-13 00:00:00 | ************** UNSAT ***************** | | | | MODEL "B" | | | | 1) PLEASE NOTE EITHER MISSING EGRESS | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | PER 210-70 OF THE NEC. | | STILL MISSING FROM ATRIUM TO OUTSIDE.?? | | | | 2)NOTE: PLEASE NOTE THAT A POOL DISC | | AND POOL PANEL ARE BOTH SHOWN ON THE | | RISER DIAGRAM? PLEASE NOTE THAT POOL | | PANEL IS STILL NOT SHOWN ON POOL PANEL., | | POOL PANEL IS BEING SHOWN IN GARAGE AND | | THE POOL PANEL DISC IS SHOWN AT THE | | REAR OF HOUSE?? PLEASE CORRELATE | | LOCATIONS. | | | | 3)NOTE: PLEASE NOTE THAT POOL PANEL IS | | BEING FED WITHTWO "HOTS"? PLEASE | | CLARIFY WHERE NEUTRAL AND EQUIPMENT | | GROUNDING CONDUCTOR, | | | | 4)NOTE: PLEASE NOTE THAT LOAD CALCULATIO | | NS NEED TO BE GONE OVER AND DONE PER | | NEC(220), | | PLEASE NOTE, 40% DERATING SEEMS TO BE | | TOO LOW. PLEASE RECONFIGURE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|