Date Text
2002-02-13 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT A-02 PLUMBING RISER DIAGRAM DOES
 NOT MATCH FLOOR PLAN. BATH #2 SHOWS VTR
 ON FLOOR PLAN BUT NOT ON RISER.
 2) SHT A-02 RISER DIA. TUB BATH #2 NOT
 VENTED
 3) SHT A-02 LAVS IN M/BATH "S" TRAPPED,
 SED 1001.5.2
 4) SHT A-02 TUB NOT VENTED ON FLOOR PLAN
 AND SHOWS A HORIZONTAL DRY VENT ON RISER
 SPC SEC 906.2.1.
 5) SHT A-02 RISER DIAGRAM, LAUNDRY SINK
 NOT VENTED AND W/M SHOWS TRAP UNDER-
 GROUND. IS W/M TRAP GOING TO BE U/G?
 6) SHT A-02 DISHWASHER NOT TRAPPED ON
 RISER. D/W SHOULD DRAIN TO GARBAGE DISP.
 OR TAILPIECE AT KITCHEN SINK.
 7) SHT A-02 RISER DIA. TRAPS FOR KITCHEN
 SINK ARE UNDERGROUND. PLEASE SHOW TRAPS
 ON STACK ABOVE GROUND.
 8) SHT A-02 MASTER BATH HORIZONTAL DRY
 VENT NOT ALLOWED. SEC 906.2.1. 3" DOUBLE
 LAV NOT VENTED PROPERLY.
  