2002-02-13 00:00:00 | *************** UNSAT **************** |
| |
| REVIEW FOR MODEL "B" |
| |
| PLEASE NOTE THAT SOME NOTES WERE ADDRESS |
| -ED AND OTHER NOT. PLEASE NOTE OTHER |
| CHANGES WERE MADE AND NOW HAVE COMMENTS |
| TO BE ADDRESSED. |
| |
| 1)NOTE: PLEASE NOTE THAT SOME REQ`D |
| EGRESS LIGHTING WAS STILL NOT ADDRESSED. |
| 210-70 SOME SHOWN AS OPT?? MISSING OTHER |
| -S |
| 2) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| MISSING IN SOME LOCATIONS. |
| |
| 3)NOTE: PLEASE NOTE GARAGE OUTLET NEEDS |
| TO BE SHOWN AS GFI. PER 210-8 |
| |
| 4)NOTE: PLEASE NOTE MISSINGLT FOR |
| ATTIC ACCESSIN BEDROOM CLOSET. 210-70 |
| |
| 5)NOTE: PLEASE NOTE, LOAD CALCUALTIONS |
| NEED TO BE SHOWN PER 220. PLEASE NOTE |
| DERATING OF AHU TWICE? AT 65% |
| PLEASE NOTE TOTAL KW DIVIDED BY 120V |
| ON A 230/240V SERVICE? |
| |
| 6)NOTE: PLEASE NOTE THAT RISER SHOWS |
| 3/0`S TO 30A POOL PANEL? PLEASE SHOW |
| OCP AND CONDUCTOR SIZES ON PANEL SCHED- |
| -ULE. PLEASE ALSO SHOW POOL PANEL ON |
| PLANS. |
| |
| 7)NOTE: PLEASE NOTE RISER NOW SHOWS AN |
| EQUIPMENT GROUNDING CONDUCTOR FROM METER |
| TO MAIN DISC? PLEASE NOTE THAT THIS IS |
| PARALLELING THE NEUTRAL. |
| |
| 8) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50./FOOTER STEEL. |
| |
| 9)NOTE: PLEASE NOTE PLANS STILL SHOW |
| NOTE ON RIGHT THAT REFERENCES WRONG NEC |
| ART FOR KITCHEN? PLEASE SEE 210-11-C-1 |
| NOT 210-52D(BATHS) |
| |
| 10)NOTE: PLEASE NOTE MISSING HALLWAY |
| OUTLET PER 210-52H |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |