2002-01-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 **NOTE**
 MODELS B,C,D AND E HAVE BEEN REVIEWED
 UNDER THE STANDARD BUILDING CODE, ANY
 PERMIT APPLICATIONS, FOR THESE MODELS,
 RECEIVED ON OR AFTER MARCH 1, 2002 WILL
 BE REVIEWED UNDER THE FLORIDA BUILDING
 CODE 2001.
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SBC* 104.2.1&3ALL MODELS. SUBMITTED
 PLANS THAT INCLUDE AN ARCHITECT/ENGINEER
 TITLE BLOCK SHALL INCORPORATE AN
 EMBOSSED SEAL, DATE AND WET SIGNATURE OF
 THE DESIGNER (471.025 AND 481.221 F.S.)
  
 4) SBC* 1804.2ALL MODELS.SUBMIT A
 SOIL TEST REPORT.
  
 5) SHEET A10 GENERAL DETAILS. THIS SHEET
 NUMBER/TITLE COMBINATION IS USED FOR TWO
 SEPARATE SHEETS CONTAINING DIFFERENT
 DETAILS.THE TITLE/NUMBER SHALL BE
 AMENDED TO DIFFERENTIATE BETWEEN SHEETS
  
 6) SBC 705.1.3OPENING PROTECTIVES.
 TABLE 600 REQUIRES THE GLASS BLOCK
 WINDOWS ON 'COMMON PROPERTY LINES' TO BE
 HAVE 1 HOUR FIRE RESISTANCE RATING.
 SUBMIT ADDITIONAL INFORMATION TO JUSTIFY
 THE PROPOSED GLASS BLOCKS.
  
 7) SBC* 104.2.2MODEL B. THE ELEVATIONS
 SHALL INCLUDE VIEWS OF THE WINDOWS OVER-
 LOOKING THE ATRIUM.
  
 8) SBC 1005.4.4MODEL B.THE MINIMUM
 CLEAR WIDTH OF AN EMERGENCY EGRESS
 WINDOW IS 20".ON SHEET A-03, FLOOR
 LAYOUT, THE BED 2 WINDOW (TYPE D) TO THE
 ATRIUM IS SHOWN ON THE WINDOW SCHEDULE
 AS 62" WIDE.THIS IS TOO WIDE TO BE
 ACCOMMODATED IN THIS LENGTH OF WALL.
 REVISE TO DEMONSTRATE COMPLIANCE.
  
 9) SBC* 1005.4.2MODELS B AND D.THE
 ATRIUM GATE MUST ALLOW EMERGENCY ESCAPE,
 FROM BED 2, WITHOUT THE USE OF SEPARATE
 TOOLS OR KEYS.THE DOOR TYPE ELEVATION
 DOES NOT APPEAR TO SHOW THE SPECIFIED
 TYPE E DOOR AS BEING A GATE.AMEND THE
 DOOR SCHEDULE AS APPROPRIATE.
  
 10) MODEL B.SHEET A-06, ELEVATIONS,
 SHOWS A KITCHEN WINDOW AND LIVING ROOM
 PATIO DOORS THAT ARE NOT SHOWN ON THE
 FLOOR PLAN (SHEET A-03).SHOW CORRECT
 ARRANGEMENT.
  
 11) MODELS B AND C.WINDOWS AND
 EXTERIOR DOORS.SOME OF THE REFERENCES
 SHOWN ON THE ELEVATIONS DO NOT CORRELATE
 TO THOSE ON THE FLOOR PLANS AND/OR THE
 DOOR/WINDOW SCHEDULES. CORRECT THOSE
 REFERENCES CONCERNED, INCLUDING, BUT NOT
 LIMITED TO, MODEL B ATRUIM GATE, LIVING
 ROOM WINDOW, FAMILY ROOM PATIO DOOR AND
 FAMILY ROOM WINDOW, AND MODEL C MASTER
 BED WALK-IN CLOSET WINDOW.ALSO, THE
 MODEL B DOOR TYPE ELEVATION FOR THE
 ATRIUM GATE DOES NOT CORRELATE TO THE
 FLOOR PLAN OR LEFT ELEVATION.
  
 12) PROVISO:PRODUCT APPROVAL (ACCEPT-
 ANCE NO 99-1110.04) FOR SERIES 6000
 ALUMINUM FIXED WINDOW.DRAWING NO 548,
 SHEET 2 OF 4 IS MISSING.
  
 13) PRODUCT APPROVALS.SUBMIT PRODUCT
 APPROVALS APPLICABLE TO EACH OF THE
 PROPOSED WINDOW AND EXTERIOR DOOR TYPES.
 THE MISSING PRODUCT APPROVALS INCLUDE,
 AMONG OTHERS, THE WOOD ENTRANCE DOORS
 AND THE HORIZONTAL SLIDING WINDOWS.
  
 14) ACCORDING TO THE DOOR SCHEDULES THE
 SUBMITTED PRODUCT APPROVAL (ACCEPTANCE
 NO 99-0311.01) FOR THE 'CONSTRUCTION
 SERIES FLUSH OUTSWING RESIDENTIAL STEEL
 DOOR-IMPACT' IS NOT APPLICABLE TO MODEL
 B, C, D OR E.
  
 15) THE SUBMITTED ROOF TILE PRODUCT
 APPROVAL FOR INTERLOCKING ROLL CONCRETE
 TILES DOES NOT CORRELATE TO THE
 ELEVATIONS WHICH SHOW "SPANISH S CEMENT
 TILE".SUBMIT AN APPROPRIATE PRODUCT
 APPROVAL.
  
 16) SBC 1606.2SPECIFY ROOF TILE
 FASTENINGS.
  
 17) MODEL B.ROOF TRUSS SHOP DRAWING
 01448 SHOWS A NARROW ROOF ARRANGEMENT
 OVER THE ENTRANCE FOYER THAT DOES NOT
 REFLECT THE ROOF ARRANGEMENT SHOWN ON
 THE ROOF FRAMING PLAN AND ELEVATIONS.
  
 18) ALL MODELS.TRUSS ANCHOR SCHEDULE.
 USP RT161T IS NOT A VALID USP REFERENCE.
 SIMPSON MTT27B IS NOT A VALID REFERENCE.
 SPECIFY FULL REFERENCE OF USP NFM.
  
 19) SHEET A-05, ROOF FRAMING PLAN.THE
 BEAM SCHEDULE DOES NOT GIVE DETAILS OF
 PATIO BEAMS REF 8F161B.REVISE TO SHOW
 BEAM TYPE.
  
 20) SBC 2309.7ALL MODELS.CROSS
 VENTILATION SHALL BE PROVIDED FOR EACH
 SEPERATE ATTIC SPACE.AT LEAST 50% OF
 THE REQUIRED VENTILATION AREA SHALL BE
 AT A LEVEL NO LESS THAN 3FT ABOVE THE
 EAVES VENTS.
  
 21) SBC 2405.1MODELS B,C,D AND E.THE
 GLASS IN THE MASTER BED SHOWER DOOR AND
 WALLS SHALL BE SAFETY GLASS IN
 COMPLIANCE WITH THE CONSUMER PRODUCT
 SAFETY COMMISSION 16-CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201)
  
 22) FL ENERGY CODE 103.1.2THE
 ARCHITECT, OWNER OR HIS/HER LEGALLY
 DESIGNATED AGENT SHALL SIGN THE ENERGY
 CODE COMPLIANCE CERTIFICATE.
  
 23) FL ENERGY CODE 603.1.ABC.1
 MODELS B, C, D AND E.THE GARAGE DOOR
 FALLS WITHIN THE DEFINITION OF AN
 'ADJACENT' DOOR (SECT. 202 DEFINITIONS)
 AND SHALL BE SOLID CORE OR INSULATED.
 THE DOOR SCHEDULE REFERENCE MARK GIVEN
 IS '8' WHICH IS SHOWN AS A TYPE F DOOR.
 THE DOOR TYPE ELEVATIONS SHOW TYPE F AS
 BEING A DOUBLE DOOR.CORRECTION REQ'D.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499