Date |
Text |
2001-12-20 00:00:00 | ************* UNSAT ******************** |
| |
| 1)NOTE: PLEASE NOTE THAT SEPARATE PLANS |
| NEED TO BE SUBMITTED FOR EACH SFH. |
| |
| 2)NOTE: PLEASE NOTE LOAD SHOWN FOR MAIN |
| PANEL ABOVE 200AMPS. MISPRINT FROM |
| LOAD CALCAULTIONS. |
| |
| 3)NOTE: PLEASE NOTE OCP FOR WATER HEATER |
| AT 125% PER 422-13. CORRELATE OCP W/ |
| WIRE SIZE. |
| |
| 4)NOTE: PLEASE NOTE MISSING EGRESS LIGHT |
| -ING IN MANY LOCATIONS, PLEASE ALSO NOTE |
| SOME AREAS(KITCHEN) SHOW LTS AS OPTS. |
| WHEN REQ`D BY 210-70. OUTSIDE, HALL, |
| ETC. |
| |
| 5)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| A/C COND UNIT PER 309.2 OF THE MECH CODE |
| |
| |
| 6)NOTE: PLEASE NOTE THAT PLANS NEED TO |
| SHOW MAIN DISC NEXT TO METERCAN AS SHOWN |
| ON RISER DIAGRAM. |
| |
| 7) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210-8-A-6. |
| PLEASE NOTE THAT NOTES NEED TO NOTE |
| CORRECT ART. NOTED AS 210-52D AND THAT |
| ART IS FOR BATHS. |
| |
| 8) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| PLEASE NOTE PLAN NOTES MENTION 210-52-D |
| SHOULD ALSO READ 210-11-C-3. AS LONG |
| AS CIRCUIT(S) IS SHOWN ON PANEL SCHEDULE |
| THEN NOT NESS TO PLACE IN NOTES. |
| |
| 9)NOTE: PLEASE CLARIFY MISSING EQUIPMENT |
| GROUNDING CONDUCTOR BETWEEN MAIN PANEL |
| AND POOL PANEL./250-122 |
| |
| 10)NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| MISSING IN MANY LOCATIONS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |