Plan Review Notes
Plan Review Notes For Permit 01111002
Permit Number 01111002
Review Stop E
Sequence Number 1
Notes
Date Text
2001-12-20 00:00:00************* UNSAT ********************
  
 1)NOTE: PLEASE NOTE THAT SEPARATE PLANS
 NEED TO BE SUBMITTED FOR EACH SFH.
  
 2)NOTE: PLEASE NOTE LOAD SHOWN FOR MAIN
 PANEL ABOVE 200AMPS. MISPRINT FROM
 LOAD CALCAULTIONS.
  
 3)NOTE: PLEASE NOTE OCP FOR WATER HEATER
 AT 125% PER 422-13. CORRELATE OCP W/
 WIRE SIZE.
  
 4)NOTE: PLEASE NOTE MISSING EGRESS LIGHT
 -ING IN MANY LOCATIONS, PLEASE ALSO NOTE
 SOME AREAS(KITCHEN) SHOW LTS AS OPTS.
 WHEN REQ`D BY 210-70. OUTSIDE, HALL,
 ETC.
  
 5)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C COND UNIT PER 309.2 OF THE MECH CODE
  
  
 6)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW MAIN DISC NEXT TO METERCAN AS SHOWN
 ON RISER DIAGRAM.
  
 7) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 PLEASE NOTE THAT NOTES NEED TO NOTE
 CORRECT ART. NOTED AS 210-52D AND THAT
 ART IS FOR BATHS.
  
 8) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 PLEASE NOTE PLAN NOTES MENTION 210-52-D
 SHOULD ALSO READ 210-11-C-3. AS LONG
 AS CIRCUIT(S) IS SHOWN ON PANEL SCHEDULE
 THEN NOT NESS TO PLACE IN NOTES.
  
 9)NOTE: PLEASE CLARIFY MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN PANEL
 AND POOL PANEL./250-122
  
 10)NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING IN MANY LOCATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372