Plan Review Notes
Plan Review Notes For Permit 01110913
Permit Number 01110913
Review Stop M
Sequence Number 1
Notes
Date Text
2001-11-30 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-1989.
  
 2.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.PLEASE SUBMIT MANUFACTURER SUBMITTAL
 DATA FOR THE CONDENSER UNIT RACK.
 NOTE, 18" MINIMUM BETWEEN ROOF
 SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL. (COUNTYWIDE AMENDMENTS
 1997 SMC 304.2.5.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.