Plan Review Notes For Permit 01110761 |
Permit Number |
01110761 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-12-03 00:00:00 | | | AS PER LOU HATTEN - BUILDING PERMIT HAS | | C.O..CONTRACTER WAS INFORMED SEPERATE | | PERMIT REQUIRED FOR DRYER EXHAUST. | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | WITH MECHANICAL PERMIT APPLICATION. | | | | | | 1.TERMINATION OF EXHAUST. | | | | 2.SIZE AND MATERIAL OF DUCT. | | | | 3.AS PER 1997 SMC 509.3, MAXIMUM | | LENGTH SHALL NOT EXCEED 25' FROM | | DRYER LOCATION TO WALL OR ROOF CAP. | | THERE SHALL BE A 5' DEDUCTION FOR | | EVERY 90 DEGREE BEND AND 2 1/2' FOR | | EVERY 45 DEGREE BEND.THE WALL OR | | ROOF CAP SHALL BE NON-SCREENED WITH | | BACK DRAFT DAMPER & MINIMUM SIZE OF | | 4". | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|