Plan Review Notes For Permit 01110755
Permit Number 01110755
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-20 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOET THAT THERE IS NO
 INDICATION ON HEATER SPECS WHICH ONE IS
 BEING INSTALLED?
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS.
 TO INCLUDE ALL NEW POOL EQUIPMENT AND
 EXSITING LOADS AND SIZE OF EXSITING
 SERVICE.215-5
  
 3)NOTE: PLEASE SHOW WIRING.CONDUITS ETC
 ON ELECTRICAL WIRING DIAGRAM. TO BE
 DONE BY ENGINEER OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372