2001-11-23 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01110637
 4600 N FLAGLER DR
 CONT: DANIELLO CONST
 TEL: 835-4788
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SBC 1804.2* SOILS REPORT GIVING THE
 MINIMUM BEARING VALUE FOR INDEPENDENT
 FOOTINGS.
  
 2)- SBC 104.2.2* ADDITIONAL INFOR. RE-
 QUIRED, THE TOTAL SQ FT OF THE CLUBHOUSE
 WITH ATTACHED PORCH ADDITION?
 ASSUMED:
 ASSEMBLY OCCUPANCY A2
 EXISTING STRUCTURE TYPE VI UNPROTECTED/
 UNSPRINKLERED
 3)- SBC SECTION 504: ASSUMED PROPERTY
 LINE, BETWEEN THE EXISTING APARTMENT &
 THE PROPOSED ADDITION. TABLE 600 ISSUES
 % OF OPENINGS TO BE ALLOWED.
  
 4)- SHOW COMPLIANCE WITH 1606.4.2*,
 EXCEPTION #1: GROUP AASSEMBLY OCUPANCY
 BUILDING, PARTS THEREOF ARE DESIGNED AS
 OPEN OR PARTIALLY ENCLOSED, SINCE THE
 CLUBHOUSE & PORCH ARE ONE STRUCTURE HOW
 IS THE IMPORTANCE FACTOR OF 1.15 BEEN
 INCORPARATED INTO THE EXISTING STRUCURE?
  
 5)- MISSING PRODUCT APPROVAL FOR THE
 ROOFING MATERIAL TO BE USED, (2 COPIES)
 SBCCI REPORT OR DADE COUNTY REPORTS ARE
 ACCEPTED BY THE CITY.
  
 6)- SBC104.2.2* SHEET A-3, A 9" DIA. CON
 CRETE PIER APPEARS WITHOUT ANY STIRRUPS.
 ARE THERE ANY REQUIRED? ACI 530 5.9.1.6
  
 7)- SAME A-3 DETAILS INDICATE CANTILEVER
 ED BEAMS THE TOP STEEL TO BE SPLICED
 AT MID POINT BETWEEN THE COLUMNS, ARE
 THE BOTTOM BARS DETAILED IN THE SAME MAN
 NER? SEE ATTACHMENT CRSE 2-15. 1 INDICAT
 ES THAT BOTTOM BARS AREN'T TO BE SPLICED
 AT MID POINTS.
  
 8)- IS THERE TOBE NO CEILING IN THE
 PORCH? WHAT TYPE OF REINFORCEMENT WILL
 BE REQUIRED FOR THE BOTTOM CHORD OF THE
 TRUSSES? WHAT BRACING REQUIREMENTS WILL
 BE REQUIRED OF THE GABLE ENDS?
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412