2001-11-23 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT# 01110637 |
| 4600 N FLAGLER DR |
| CONT: DANIELLO CONST |
| TEL: 835-4788 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| |
| 1)- SBC 1804.2* SOILS REPORT GIVING THE |
| MINIMUM BEARING VALUE FOR INDEPENDENT |
| FOOTINGS. |
| |
| 2)- SBC 104.2.2* ADDITIONAL INFOR. RE- |
| QUIRED, THE TOTAL SQ FT OF THE CLUBHOUSE |
| WITH ATTACHED PORCH ADDITION? |
| ASSUMED: |
| ASSEMBLY OCCUPANCY A2 |
| EXISTING STRUCTURE TYPE VI UNPROTECTED/ |
| UNSPRINKLERED |
| 3)- SBC SECTION 504: ASSUMED PROPERTY |
| LINE, BETWEEN THE EXISTING APARTMENT & |
| THE PROPOSED ADDITION. TABLE 600 ISSUES |
| % OF OPENINGS TO BE ALLOWED. |
| |
| 4)- SHOW COMPLIANCE WITH 1606.4.2*, |
| EXCEPTION #1: GROUP AASSEMBLY OCUPANCY |
| BUILDING, PARTS THEREOF ARE DESIGNED AS |
| OPEN OR PARTIALLY ENCLOSED, SINCE THE |
| CLUBHOUSE & PORCH ARE ONE STRUCTURE HOW |
| IS THE IMPORTANCE FACTOR OF 1.15 BEEN |
| INCORPARATED INTO THE EXISTING STRUCURE? |
| |
| 5)- MISSING PRODUCT APPROVAL FOR THE |
| ROOFING MATERIAL TO BE USED, (2 COPIES) |
| SBCCI REPORT OR DADE COUNTY REPORTS ARE |
| ACCEPTED BY THE CITY. |
| |
| 6)- SBC104.2.2* SHEET A-3, A 9" DIA. CON |
| CRETE PIER APPEARS WITHOUT ANY STIRRUPS. |
| ARE THERE ANY REQUIRED? ACI 530 5.9.1.6 |
| |
| 7)- SAME A-3 DETAILS INDICATE CANTILEVER |
| ED BEAMS THE TOP STEEL TO BE SPLICED |
| AT MID POINT BETWEEN THE COLUMNS, ARE |
| THE BOTTOM BARS DETAILED IN THE SAME MAN |
| NER? SEE ATTACHMENT CRSE 2-15. 1 INDICAT |
| ES THAT BOTTOM BARS AREN'T TO BE SPLICED |
| AT MID POINTS. |
| |
| 8)- IS THERE TOBE NO CEILING IN THE |
| PORCH? WHAT TYPE OF REINFORCEMENT WILL |
| BE REQUIRED FOR THE BOTTOM CHORD OF THE |
| TRUSSES? WHAT BRACING REQUIREMENTS WILL |
| BE REQUIRED OF THE GABLE ENDS? |