Plan Review Notes
Plan Review Notes For Permit 01110620
Permit Number 01110620
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-11-20 00:00:001) NO CUT-SHEETS PROVIDED FOR FIRE
 SPRINKLER HEADS PLANNED FOR USE. PLEASE
 PROVIDE CUT-SHEETS.
 2) PROVIDE DETAILS FOR FIRE SPRINKLER
 INSTALLATIONS FOR DUMBWAITER AND TRASH
 CHUTE(S).
 3) PLEASE INDICATE IF THE ONE FIRE
 DEPARTMENT CONNECTION WILL SERVICE ALL
 OF THE BUILDINGS LOCATED ON THE CAMPUS.
 4) NO FIRE SPRINKLER PROTECTION PROVIDED
 FOR IT EQUIPMENT ROOM. FM 200 SYSTEM
 IS NOTED BUT CANNOT BE USED IN LIEU OF
 REQUIRED FIRE SPRINKLER PROTECTION.
 5) HOW WILL PIPE PENETRATIONS BE SEALED
 THRU RATED FIRE WALLS, ETC. WHO'S
 RESPONSIBLE FOR IT.
 6) PLEASE CLEARLY INDICATE WHY NO
 FIRE STANDPIPE SYSTEM IS PRESENT IN THE
 GARAGE. IF THE GARAGE IS THREE STORIES
 AND MORE THAN FIFTY FEET IN HEIGHT A
 STANDPIPE SYSTEM WOULD BE REQUIRED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910