Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-20 00:00:00 | 1) NO CUT-SHEETS PROVIDED FOR FIRE | | SPRINKLER HEADS PLANNED FOR USE. PLEASE | | PROVIDE CUT-SHEETS. | | 2) PROVIDE DETAILS FOR FIRE SPRINKLER | | INSTALLATIONS FOR DUMBWAITER AND TRASH | | CHUTE(S). | | 3) PLEASE INDICATE IF THE ONE FIRE | | DEPARTMENT CONNECTION WILL SERVICE ALL | | OF THE BUILDINGS LOCATED ON THE CAMPUS. | | 4) NO FIRE SPRINKLER PROTECTION PROVIDED | | FOR IT EQUIPMENT ROOM. FM 200 SYSTEM | | IS NOTED BUT CANNOT BE USED IN LIEU OF | | REQUIRED FIRE SPRINKLER PROTECTION. | | 5) HOW WILL PIPE PENETRATIONS BE SEALED | | THRU RATED FIRE WALLS, ETC. WHO'S | | RESPONSIBLE FOR IT. | | 6) PLEASE CLEARLY INDICATE WHY NO | | FIRE STANDPIPE SYSTEM IS PRESENT IN THE | | GARAGE. IF THE GARAGE IS THREE STORIES | | AND MORE THAN FIFTY FEET IN HEIGHT A | | STANDPIPE SYSTEM WOULD BE REQUIRED. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|