Plan Review Notes For Permit 01110498 |
Permit Number |
01110498 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-21 00:00:00 | ********************PROVISO************* | | | | | | ACCESS OPENING FOR AHU SHALL BE A | | MINIMUM OF 22" X 36" CONTINUOUS FROM | | THE OPENING TO EQUIPMENT AND ITS | | CONTROLS. | | | | ALL AHU INSTALLED IN ATTIC SHALL HAVE AN | | ACCESSIBLE DISCONNECT SWITCH AND A | | 110-120 VOLT A/C GROUNDING TYPE | | CONVENIENCE OUTLET.A LIGHT SHALL BE | | LOCTED ON THE SERVICE SIDE OF THE | | EQUIPMENT WHICH IS CONTROLLED BY A | | SWITCH LOCATED AT THE ACCESS OPENING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|