Plan Review Notes
Plan Review Notes For Permit 01110498
Permit Number 01110498
Review Stop M
Sequence Number 1
Notes
Date Text
2001-11-21 00:00:00********************PROVISO*************
  
  
 ACCESS OPENING FOR AHU SHALL BE A
 MINIMUM OF 22" X 36" CONTINUOUS FROM
 THE OPENING TO EQUIPMENT AND ITS
 CONTROLS.
  
 ALL AHU INSTALLED IN ATTIC SHALL HAVE AN
 ACCESSIBLE DISCONNECT SWITCH AND A
 110-120 VOLT A/C GROUNDING TYPE
 CONVENIENCE OUTLET.A LIGHT SHALL BE
 LOCTED ON THE SERVICE SIDE OF THE
 EQUIPMENT WHICH IS CONTROLLED BY A
 SWITCH LOCATED AT THE ACCESS OPENING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved