Plan Review Notes For Permit 01110457
Permit Number 01110457
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE P-1 GENERAL NOTES #16, AIR
 CHAMBERS ARE QUICK FIX AND REQUIRE ACC-
 ESS PANELS AND SHALL BE RECHARGEABLE PER
 SPC 607.8.3. WATER HAMMER ARRESTORS
 SHOULD BE USED AND SHALL BE SIZED AND
 LOCATED CLOSE TO FIXTURES PER MANUFACT-
 URE INSTALLATION INSTRUCTIONS AND PDI-WH
 201.
 2) PAGE P-1 THREE COMPARTMENT COOLER IN
 BAR AREA SHALL INDIRECTLY DRAIN INTO A
 FLOOR SINK PER SPC SEC 804.1. PLEASE
 CHANGE DRAIN TO REFLECT INDIRECT DRAIN.
 SANITARY RISER DIAGRAM REQUIRED FOR PIP-
 ING IN BAR AREA.
 3) PAGE P-1 PLEASE SHOW LOCATION OF
 WATER HEATER FOR NEW RESTROOMS AND BAR
 SINK. IF LOCATED ON A SHELF OR ABOVE THE
 CEILING A PERMINANT SHIPS LADDER AND A
 WORKING PLATFORM MINIMUM 30"X30" SHALL
 BE REQUIRED AND DETAILS REQUIRED.
  
 REVIEW BY KEN STEVENS