1 |
|
Notes |
Date |
Text |
2001-11-19 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) PAGE P-1 GENERAL NOTES #16, AIR | | CHAMBERS ARE QUICK FIX AND REQUIRE ACC- | | ESS PANELS AND SHALL BE RECHARGEABLE PER | | SPC 607.8.3. WATER HAMMER ARRESTORS | | SHOULD BE USED AND SHALL BE SIZED AND | | LOCATED CLOSE TO FIXTURES PER MANUFACT- | | URE INSTALLATION INSTRUCTIONS AND PDI-WH | | 201. | | 2) PAGE P-1 THREE COMPARTMENT COOLER IN | | BAR AREA SHALL INDIRECTLY DRAIN INTO A | | FLOOR SINK PER SPC SEC 804.1. PLEASE | | CHANGE DRAIN TO REFLECT INDIRECT DRAIN. | | SANITARY RISER DIAGRAM REQUIRED FOR PIP- | | ING IN BAR AREA. | | 3) PAGE P-1 PLEASE SHOW LOCATION OF | | WATER HEATER FOR NEW RESTROOMS AND BAR | | SINK. IF LOCATED ON A SHELF OR ABOVE THE | | CEILING A PERMINANT SHIPS LADDER AND A | | WORKING PLATFORM MINIMUM 30"X30" SHALL | | BE REQUIRED AND DETAILS REQUIRED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|