Plan Review Notes
Plan Review Notes For Permit 01110351
Permit Number 01110351
Review Stop E
Sequence Number 2
Notes
Date Text
2001-12-27 00:00:001)PLEASE PROVIDE AN A.I.C. RATING FOR
 THE SERVICE CONNECTION AT MDP. AS PER
 110-9&110-10.
 2)PERMIT APPLICATION DOES NOT INCLUDE
 WIRING NEW A/C'S OR INTERIOR WIRING OF
 UPPER UNIT IN THE PROJECT DESCRIPTION.
 3)THE ENGINEER'S TITLE BLOCK MUST BE ON
 THE REVISED RISER DIAGRAM ALONG WITH HIS
 STAMP AS PER FS/FAC 61G 15-23.002
 4)PANEL SCHEDULES ON ARE ILLEGIBLE.
 5)NOTE "1" ON THE RISER DIAGRAM
 INDICATES #1 CU CONDUCTORS TERMINATING
 ON A 50AMP CIRCUIT BREAKER !!!
 6)METER ENCLOSURE DOES NOT SHOW AMPERAGE
 RATING, PLEASE INCLUDE.
 7)THE PLANS DON'T SHOW A LOAD
 CALCULATION FOR THE HOUSE PANEL, PLEASE
 ADD.
 8)THE NEW PANEL SHOWN IN THE UPPER
 LIVING SPACE MUST COMPLY WITH 230-79D.