Plan Review Notes For Permit 01110351 |
Permit Number |
01110351 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-12-27 00:00:00 | 1)PLEASE PROVIDE AN A.I.C. RATING FOR | | THE SERVICE CONNECTION AT MDP. AS PER | | 110-9&110-10. | | 2)PERMIT APPLICATION DOES NOT INCLUDE | | WIRING NEW A/C'S OR INTERIOR WIRING OF | | UPPER UNIT IN THE PROJECT DESCRIPTION. | | 3)THE ENGINEER'S TITLE BLOCK MUST BE ON | | THE REVISED RISER DIAGRAM ALONG WITH HIS | | STAMP AS PER FS/FAC 61G 15-23.002 | | 4)PANEL SCHEDULES ON ARE ILLEGIBLE. | | 5)NOTE "1" ON THE RISER DIAGRAM | | INDICATES #1 CU CONDUCTORS TERMINATING | | ON A 50AMP CIRCUIT BREAKER !!! | | 6)METER ENCLOSURE DOES NOT SHOW AMPERAGE | | RATING, PLEASE INCLUDE. | | 7)THE PLANS DON'T SHOW A LOAD | | CALCULATION FOR THE HOUSE PANEL, PLEASE | | ADD. | | 8)THE NEW PANEL SHOWN IN THE UPPER | | LIVING SPACE MUST COMPLY WITH 230-79D. |
|