Plan Review Notes
Plan Review Notes For Permit 01110351
Permit Number 01110351
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-16 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 COMPLETE FOR COMPLETE PLAN REVIEW.
  
 2)NOTE: PLEASE NOTE THAT MIN SERVICE
 SIZE FOR UNITS. 230-79 C&D.
  
 3)NOTE: PLEASE NOTE ONE SET OF CONDCUTOR
 -S COMING FROM MDP TO GUTTER???
 PLEASE CORRECT.
  
 4)NOTE: PLEASE SUBMIT ALL CONDCUTOR
 SIZES FOR SERVICE ENTRANCE. 215-5
  
  
  
  
 6)NOTE: PLEASE CLARIFY IF PANELS SHOWN
 AS "EXT" IS EXSITING OR EXTERIOR?
  
 7)NOTE: PLEASE OUTLETS SHOWN IN THE
 MIDDLE OF FLOOR IN DINING ROOM.?
  
 8)NOTE: PLEASE NOTE SMOKE DETECTORS
 INSIDE AND OUTSIDE BEDROOM. NFPA-72
 2-2.1.1.1
  
 9)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDINGPER 250-122 BETWEEN
 MAIN/MDP AND PANELS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372