Plan Review Notes For Permit 01110351 |
Permit Number |
01110351 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-16 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | COMPLETE FOR COMPLETE PLAN REVIEW. | | | | 2)NOTE: PLEASE NOTE THAT MIN SERVICE | | SIZE FOR UNITS. 230-79 C&D. | | | | 3)NOTE: PLEASE NOTE ONE SET OF CONDCUTOR | | -S COMING FROM MDP TO GUTTER??? | | PLEASE CORRECT. | | | | 4)NOTE: PLEASE SUBMIT ALL CONDCUTOR | | SIZES FOR SERVICE ENTRANCE. 215-5 | | | | | | | | | | 6)NOTE: PLEASE CLARIFY IF PANELS SHOWN | | AS "EXT" IS EXSITING OR EXTERIOR? | | | | 7)NOTE: PLEASE OUTLETS SHOWN IN THE | | MIDDLE OF FLOOR IN DINING ROOM.? | | | | 8)NOTE: PLEASE NOTE SMOKE DETECTORS | | INSIDE AND OUTSIDE BEDROOM. NFPA-72 | | 2-2.1.1.1 | | | | 9)NOTE: PLEASE CLARIFY MEANS OF EQUIP- | | -MENT GROUNDINGPER 250-122 BETWEEN | | MAIN/MDP AND PANELS? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|