Notes
Date Text
2002-02-11 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE PROVIDE A COPY OF THE CONTRACT
 SO SEC 4.1.6(2), 20 PERCENT OVER CONT.
 CAN BE ESTABLISHED.
 2) PLEASE SHOW CLEAR FLOOR SPACE FOR ALL
 PLUMBING FIXTURES.
 3) TURNING RADIUS REQUIRED TO BE 5"0",
 NOT 48" AS SHOWN.
 4) PLEASE SHOW DETAIL FOR BACKING FOR
 GRAB BARS.
 5) PLEASE GIVE MEASUREMENTS FOR TOILET
 ROOMS. GIVE FINISHED MEASURMENTS FOR ALL
 SHOWERS.
 6) PLEASE SUBMIT RISER DIAGRAMS THAT ARE
 CLEAR AND READABLE. PLEASE INDICATE
 WHICH BATHROOM IS WHICH ON RISER DIAGRAM
 3 NEW BATHROOMS BUT 4 SHOWN ON RISER DIA
 GRAM. HOW DOES 4TH BATHROOM TIE INTO THE
 REST OF THE RISER?
 7) SANITARY RISER SHOWS SLOP SINKS BUT
 FLOOR PLAN DOES NOT SHOW ANY.
 8) PLEASE GIVE AN ELEVATION FOR W/HEATER
 IS IT GOING TO BE ON THE FLOOR? IF ON
 SHELF A PERMINATE SHIPS LADDER WILL BE
 REQUIRED TO MAKE THE HEATER ACCESSIBLE.
  
 REVIEW BY KEN STEVENS