2002-02-11 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01110345 |
| 1608 S DIXIE HWY |
| CONT: CHEROKEE BUILDERS |
| TELL: (561) 346-1346 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| FL ACC= FLORIDA ACCESSIBILITY CODE 1997 |
| |
| 1)- FLORIDA STATE STATUTE 481.229 |
| EXCEPTION 1-C: AN ARCHITECT SHALL BE RE- |
| QUIRED FOR WORK IN EXCESS OF $25,000.00 |
| THE ELECTRICAL NOTE #3 INDICATES VALUE |
| TO LOW. THE CALCULATED VALUE IS CLOSE TO |
| $79,000.00. |
| |
| 2)- SBC 1104.2.2 NOT ENOUDH INFORMATION |
| MISSING DOOR INFO, ROOM DIMENSIONS & |
| SCALE OF DRAWING,ETC. |
| |
| 3)- THE OWNER INDICATED THERE TO BE |
| EXISTING FIRE SPRINKLERS, NO INFORMATION |
| SUPPLIED. |
| |
| 4)- SBC TABLE 803.3 INTERIOR FINISH SCHE |
| DULE NOT GIVEN. |
| |
| 5)- THERE IS A DEAD END CORRIDOR NEXT TO |
| STORAGE AREA #1. |
| |
| 6)- HANDICAPPED RESTROOMS, THERE ISN'T |
| A 5'-0" TURNING RADIUS, NO INFORMATION |
| ON BACKING HAND RAILS NOR OTHER ELEMENTS |
| THAT MAKE UP A HANDICAPPED RESTROOM. |
| |
| 7)- FL ACC CODE 4.13.6 THE PLANS DO NOT |
| HAVE THE MANEUVERING CLEARENCES AT |
| DOORWAYS. |
| |
| 8)- THE PLANS ARE MISSING TENANT SEPERAT |
| ION, RATING, SEPERATION BETWEEN STORAGE |
| AREA AND THE COMMON EXIT ACCESS CORRIDOR |
| |
| 9)- MISSING FLOOR/ CEILING ASSEMBLY |
| TENANT SEPERATION. |
| |
| 10)- VENTILATION FOR RESTROOM? |
| |
| 11)- PUBLIC RESTROOMS SBC1204.3 |
| TO BE LINED WITH AN NONABSORBANT MATER- |
| IAL TO A HEIGTH OF 4'-0" ABOVE THE |
| FLOOR. |
| 12)- THERE IS A ROOM BETWEEN RESTROOM |
| B & C THAT HAS NO ENTRY? |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096 X8412 |