 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE THE FOLLOWING
 PLANS AND THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 1.INDICATE SIZE, MATERIAL, LAYOUT AND
 CFM OF ANY NEW DUCT WORK TO BE
 INSTALLED.
  
 2.SUBMIT MANUFACTURER DATA FOR EXHAUST
 FANS BEING INSTALLED. (1997 SMC
 503.3.1)
  
 3.SHOW COMPLIANCE WITH 1997 SMC 501.2.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.
  
  
 NO AIR SUPPLIED TO OFFICE OR RESTROOM.
  
 SHOW COMPLIANCE WITH 1997 SMC 501.2, AIR
 MAKE-UP FOR RESTROOM.
  
 PROVISO WRITTEN ON PLAN:
  
 1. NO COMBUSTIBLES ABOVE THE CEILING IN
 THE RETURN AIR PLENUM.
 1997 SMC 609.1.1.
  
 2. FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.
 NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.