Plan Review Notes For Permit 01110345 |
Permit Number |
01110345 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-19 00:00:00 | | | | | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW.PLEASE PROVIDE THE FOLLOWING | | PLANS AND THE FOLLOWING INFORMATION | | WITH MECHANICAL PERMIT APPLICATION. | | | | 1.INDICATE SIZE, MATERIAL, LAYOUT AND | | CFM OF ANY NEW DUCT WORK TO BE | | INSTALLED. | | | | 2.SUBMIT MANUFACTURER DATA FOR EXHAUST | | FANS BEING INSTALLED. (1997 SMC | | 503.3.1) | | | | 3.SHOW COMPLIANCE WITH 1997 SMC 501.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. | | | | | | NO AIR SUPPLIED TO OFFICE OR RESTROOM. | | | | SHOW COMPLIANCE WITH 1997 SMC 501.2, AIR | | MAKE-UP FOR RESTROOM. | | | | PROVISO WRITTEN ON PLAN: | | | | 1. NO COMBUSTIBLES ABOVE THE CEILING IN | | THE RETURN AIR PLENUM. | | 1997 SMC 609.1.1. | | | | 2. FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | WITH NOTIFICATION TO ALARM/STROBE IN | | NORMALLY OCCUPIED AREAS. | | NFPA 90A 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|