2002-03-08 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| FL ENERGY CODE = FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 12/14/01: |
| |
| 10) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| REFER TO BUILDING PLAN REVIEW12/14/01 |
| |
| 11) --PROVISO-- |
| SBC 2308.3.2THE WINDOW HEADERS SHALL |
| BE SUPPORTED BY JACK STUDS IN ACCORDANCE |
| WITH TABLE 2308.3A |
| |
| 13) --PROVISO-- |
| SBC* 104.1.1NO ROOF COVERING SPECIFIED |
| A ROOFING PERMIT APPLICATION IS REQUIRED |
| |
| 22) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| SBC 1608.2SECTION 4/S1.SHOW/STATE |
| THE MEANS OF FIXING THE 2X4 TO THE 2X6. |
| |
| 37) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| FL ENERGY CODE 101.1.2THE ADDITION |
| SHALL COMPLY WITH FLORIDA ENERGY CODE. |
| |
| 38) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| FL ENERGY CODE 103.0COMPLIANCE SHALL |
| BE DEMONSTRATED BY SUBMITTAL OF |
| APPROPRIATE ENERGY CODE COMPLIANCE FORMS |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| ROBERT BROWN(561) 659 8096 EXT 8499 |