Plan Review Notes
Plan Review Notes For Permit 01110307
Permit Number 01110307
Review Stop B
Sequence Number 3
Notes
Date Text
2002-03-08 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/14/01:
  
 10) THIS COMMENT HAS NOT BEEN ADDRESSED.
 REFER TO BUILDING PLAN REVIEW12/14/01
  
 11) --PROVISO--
 SBC 2308.3.2THE WINDOW HEADERS SHALL
 BE SUPPORTED BY JACK STUDS IN ACCORDANCE
 WITH TABLE 2308.3A
  
 13) --PROVISO--
 SBC* 104.1.1NO ROOF COVERING SPECIFIED
 A ROOFING PERMIT APPLICATION IS REQUIRED
  
 22) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SBC 1608.2SECTION 4/S1.SHOW/STATE
 THE MEANS OF FIXING THE 2X4 TO THE 2X6.
  
 37) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FL ENERGY CODE 101.1.2THE ADDITION
 SHALL COMPLY WITH FLORIDA ENERGY CODE.
  
 38) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FL ENERGY CODE 103.0COMPLIANCE SHALL
 BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE ENERGY CODE COMPLIANCE FORMS
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 ROBERT BROWN(561) 659 8096 EXT 8499