2002-02-04 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| SBC = STANDARD BUILDING CODE 1997 |
| SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| FL ENERGY CODE = FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 12/14/01: |
| |
| 1) CHANGE OF USE FROM RESIDENTIAL TO |
| BUSINESS. IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY, PLANS STAMPED BY THEM |
| AND COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 7) **PROVISO**THIS PERMIT APPLICATION |
| SHOWS A WOOD FLOOR WHILST FOUNDATION |
| PERMIT# 01081206 SHOWS A CONCRETE SLAB. |
| UNDERFLOOR VENTILATION OF EXISTING |
| BUILDING MUST BE MAINTAINED (SBC 2304.3) |
| |
| 10) THE RESUBMITTAL DOES NOT ADDRESS |
| THIS REVIEW COMMENT. |
| |
| 11) THE RESUBMITTAL DOES NOT ADDRESS |
| THIS REVIEW COMMENT. |
| |
| 13) **PROVISO** |
| SBC* 104.1.1A SEPARATE ROOFING PERMIT |
| APPLICATION IS REQUIRED. |
| |
| 16) **PROVISO** |
| SBC 1013.6THE REVISED PLANS SHOW THE |
| REQUIRED 12" HANDRAIL EXTENSION AT THE |
| BOTTOM OF THE RAMP BUT NOT AT THE TOP OF |
| THE SLOPED SECTION. |
| |
| 17) SBC 1013.6THE HEIGHT OF THE RAMP |
| HANDRAIL IS STILL SHOWN ON SECTION 1/S1 |
| AS 26".AMEND THE HEIGHT TO BETWEEN 34" |
| AND 38". |
| |
| 19) FL ACC CODE 4.9.4(2)SECTION 11/S1 |
| SHOWS THE CORRECT REQUIREMENT FOR THE |
| STAIRCASE HANDRAILS TO CONTINUE TO SLOPE |
| PAST THE BOTTOM RISER BY A DISTANCE |
| EQUAL TO THE DEPTH OF ONE TREAD AND THEN |
| EXTEND HORIZONTALLY FOR A FURTHER 12". |
| SECTION 7/S1 DOES NOT REFLECT THIS AND |
| SHOULD ME AMENDED TO AVOID CONFUSION. |
| |
| 22) THE RESUBMITTAL DOES NOT ADDRESS |
| THIS REVIEW COMMENT. |
| |
| 28) **PROVISO**THE PLAN ON SHEET S1 |
| CORRECTLY STATES THAT THE FLOOR LEVEL OF |
| THE ADDITION IS TO MATCH THAT OF THE |
| EXISTING BUILDING.THE STEPS SHOWN ON |
| SHEET S2 'FULL HEIGHT WALL SECTION' |
| SHOULD BE DELETED TO REFLECT THIS AND |
| AVOID CONFUSION. |
| |
| 37) FL ENERGY CODE 101.1.2THE ADDITION |
| SHALL COMPLY WITH FLORIDA ENERGY CODE. |
| |
| 38) FL ENERGY CODE 103.0COMPLIANCE |
| SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| APPROPRIATE ENERGY CODE COMPLIANCE FORMS |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUERIES PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |