Plan Review Notes For Permit 01110307 |
Permit Number |
01110307 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-12-13 00:00:00 | 1) SINCE THE BUILDING WAS RESIDENTIAL | | AND IS BELIEVED TO BE PLANNED FOR | | OFFICE USE, THEN A CHANGE OF USE WILL | | BE OCCURRING. | | 2) PLEASE INDICATE EXIT SIGNS AND | | EMERGENCY LIGHT FIXTURES. | | 3) PLEASE INDICATE INTERIOR FINISH | | FOR WALLS AND CEILINGS. | | 4) DOORS USED FOR EXITING SHALL BE | | AT LEAST 32 INCHES WIDE. | | 5) PLEASE INDICATE THE TYPES OF LOCKING | | DEVICES PLANNED FOR THE EXIT DOORS. | | 6) THERE APPEARS TO BE A CONFLICT | | WITH THE DRAWINGS. ONE PAGE ILLUSTRATES | | 10 INCH TREADS AND THE OTHER ONE | | DISPLAYS FOUR TWELVE INCH TREADS. PLEASE | | BE ADVISED THAT 11 INCH TREADS ARE | | REQUIRED. | | 7) HOW IS ACCESS OBTAINED INTO THE | | ADDITION. PLEASE PROVIDE CLARITY AND | | WIDTHS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|