2001-12-11 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| PERMIT REQ'D:ADDITION |
| CHANGE OF USE FROM |
| RESIDENTIAL TO BUSINESS |
| |
| SBC = STANDARD BUILDING CODE |
| SBC*= STANDARD BUILD'G CODE (AMENDMENTS) |
| FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| FL ENERGY CODE = FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| |
| |
| ** DENOTES UPDATE TO REVIEW COMMENTS |
| FOLLOWING MEETING ON 12/13/01 WITH |
| GAY CINQUE |
| |
| 1) CHANGE OF USE FROM RESIDENTIAL TO |
| BUSINESS WILL BE SUBJECT TO IMPACT FEES. |
| |
| 2) SBC 3401.2.2.1FOR CHANGE OF |
| OCCUPANCY IN AN EXISTING BUILDING, THE |
| BUILDING, ELECTRICAL, GAS, MECHANICAL |
| AND PLUMBING SYSTEMS SHALL BE MADE TO |
| COMFORM WITH THE INTENT OF THE TECHNICAL |
| CODES |
| |
| 3) SBC 1804.1THE BASE OF THE |
| FOUNDATIONS SHALL BE AT LEAST 12" BELOW |
| FINISH GRADE. |
| ** PROPOSALS ACCEPTED UNDER FOUNDATION |
| PERMIT #01081206 |
| |
| 4) SBC 2303.1THE GROUND AROUND THE |
| BUILDING SHALL BE GRADED TO SLOPE AWAY |
| FROM IT. |
| |
| 5) SBC 2313SECTION 1/1. SPACING OF THE |
| STD ACI 90 DEGREE HOOKS SHALL BE STATED. |
| ANNOTATION TO SPECIFY THE FOUNDATION |
| WALL INFILL MATERIAL SHALL BE ADDED. |
| |
| 6) SHEET 1, NOTES.THE SPECIFIED |
| CONCRETE STANDARDS ACI 301-79, 315-80 |
| AND MASONRY STANDARD ACI 531 ARE NOT |
| REFERENCED IN SBC 1997.BASIS OF DESIGN |
| AND SPECIFICATION REQUIRES CLARIFICATION |
| |
| 7) SBC 2304.3UNDERFLOOR SPACES SHALL |
| BE VENTILATED.THE NEW ADDITION SHALL |
| NOT OBSTRUCT UNDERFLOOR VENTILATION OF |
| THE EXISTING BUILDING. |
| ** THIS PERMIT APPLICATION SHOWS A WOOD |
| FLOOR WHILST FOUNDATION PERMIT |
| #01081206 SHOWS A CONCRETE SLAB. |
| CLARIFICATION REQUIRED.UNDERFLOOR |
| VENTILATION OF EXISTING BUILDING MUST |
| BE MAINTAINED. |
| |
| 8) SBC 2307.3.1THE PROPOSED FLOOR |
| JOIST SPAN EXCEEDS THE LIMITS GIVEN IN |
| AF&PA SPAN TABLES.JUSTIFICATION BY |
| CALCULATION, INCREASED DEPTH, REDUCED |
| SPACING OR INTERMEDIATE SUPPORT IS REQ'D |
| |
| 9) SBC 2303.3THE EXTERIOR WALL SHALL |
| INCORPORATE MOISTURE PROTECTION IN THE |
| FORM OF TYPE 15 (MINIMUM) FELT OR OTHER |
| RECOGNISED MATERIAL. |
| |
| 10) SBC 2308PROVIDE DETAILS OF THE |
| MEANS OF ATTACHMENT OF THE NEW WALLS TO |
| THE EXISTING BUILDING.THE PLYWOOD |
| SHEATHING ON THE ADDITION SHALL BE MIN. |
| 5/8" THICK (SEE SBC TABLE 2308.2.2B) |
| |
| 11) SBC 2308.3.2THE WINDOW HEADERS |
| SHALL BE SUPPORTED BY JACK STUDS IN |
| ACCORDANCE WITH TABLE 2308.3A. |
| |
| 12) SBC 2309.7.2THE FLAT ROOF VOID |
| SHALL BE VENTILATED BY A NETT AREA OF |
| OPENING NOT LESS THAN 1/250 OF THE AREA |
| OF THE CEILING BELOW. |
| |
| 13) SBC 1501NO ROOF COVERING SPECIFIED |
| A ROOFING PERMIT APPLICATION IS REQUIRED |
| |
| 14) SBC 1606.1.2.1ON SHEET 1, NOTE 6, |
| DESIGN (WIND) LOAD REFERENCES BOTH |
| SBC 1997 AND ASCE 7.CONFIRM THE |
| BASIS OF DESIGN AND STATE THE BASIC |
| VELOCITY PRESSURE. |
| |
| 15) SBC 1013.9EXTERIOR RAMPS AND |
| LANDINGS SHALL BE DESIGNED SO WATER WILL |
| NOT ACCUMULATE ON THEIR SURFACES.THIS |
| SHALL BE ACCOMPLISHED WITHOUT EXCEEDING |
| A CROSS SLOPE OF 1:50(FL ACC CODE 4.3.7) |
| |
| 16) SBC 1013.6THE RAMP HANDRAILS SHALL |
| EXTEND, PARALLEL TO THE FLOOR/GROUND |
| SURFACE, AT LEAST 12" BEYOND THE TOP AND |
| BOTTOM OF THE RAMP. |
| |
| 17) SBC 1007.5 & 1013.6THE HANDRAILS |
| ON THE EXTERNAL STAIR AND RAMP SHALL BE |
| LOCATED AT A HEIGHT OF BETWEEN 34" AND |
| 38" ABOVE THE RAMP OR LEADING EDGE OF |
| THE TREAD.THE STAIRCASE HANDRAIL MAY |
| BE 42" HIGH IF IT FORMS PART OF THE |
| GUARDRAIL.THE REQUIRED HEIGHT |
| DIMENSIONS SHALL BE ADDED TO SECTION |
| 7/S1 AND AMENDED ON SECTION 1/S1 |
| |
| 18) FL ACC CODE 4.8.5(6) & 4.9.4(6)THE |
| ENDS OF THE HANDRAILS SHALL BE ROUNDED |
| OR RETURNED SMOOTHLY TO GROUND OR POST. |
| |
| 19) FL ACC CODE 4.9.4(2)THE EXTERNAL |
| STAIRCASE HANDRAILS SHALL CONTINUE TO |
| SLOPE PAST THE BOTTOM RISER FOR A |
| DISTANCE NOT LESS THAN THE DEPTH OF ONE |
| TREAD AND THEN EXTEND HORIZONTALLY FOR |
| ANOTHER 12". |
| |
| 20) SBC 1015.2THE EXTERNAL STAIRCASE |
| LANDING GUARDRAIL SHALL BE NOT LESS THAN |
| 42" HIGH.ADD DIMENSION TO SECTION 7/S1 |
| |
| 21) SBC 1015.3THE GUARDRAILS TO THE |
| EXTERNAL STAIRCASE LANDING SHALL HAVE |
| RAILS SPACED SUCH THAT A 4" SHERE |
| CANNOT PASS THROUGH ANY OPENING. |
| |
| 22) SBC 1608.2THE CONSTRUCTION OF |
| HANDRAILS AND GUARDRAILS SHALL BE |
| ADEQUATE IN STRENGTH, DURABILITY AND |
| ATTACHMENT TO RESIST THE REQUIRED LOAD |
| COMBINATIONS.DETAILS OF THE MEANS OF |
| ATTACHMENT FOR THE EXTERNAL STAIRCASE |
| AND LANDING RAILING SHALL BE SUBMITTED. |
| |
| 23) FL ACC CODE 4.8.5(4) & 4.9.4(4)THE |
| EXTERNAL STAIR AND RAMP HANDRAIL |
| GRIPPING SURFACES SHALL BE CONTINUOUS |
| AND UNINTERRUPTED BY NEWEL POSTS OR |
| OTHER OBSTRUCTIONS. |
| |
| 24) FL ACC CODE 4.9.2THE STAIR TREADS |
| SHALL BE NO LESS THAN 11" WIDE, MEASURED |
| FROM RISER TO RISER.OPEN RISERS ARE |
| NOT PERMITTED. |
| |
| 25) FL ACC CODE 4.9.3THE UNDERSIDE OF |
| THE STAIR NOSINGS SHALL NOT BE ABRUPT |
| (SEE FIGURE 18). |
| |
| 26) FL ACC CODE 4.9.6OUTSIDE STAIRS |
| AND THEIR APPROACHES SHALL BE DESIGNED |
| SO THAT WATER WILL NOT ACCUMULATE ON |
| WALKING SURFACES. |
| |
| 27) FL ACC CODE 4.1.5THE ADDITION |
| SHALL COMPLY WITH THE APPLICABLE |
| PROVISIONS OF THE MINIMUM REQUIREMENTS |
| (4.1.1 TO 4.1.3) AND THE APPLICABLE |
| TECHNICAL SPECIFICATIONS (4.2 THROUGH |
| 4.35) |
| |
| 28) FL ACC CODE 4.1.3(5)VERTICAL |
| ACCESSIBILITY SHALL BE PROVIDED.THE |
| FLOOR OF THE ADDITION SHOULD BE RAISED |
| TO MATCH THAT OF THE EXISTING BUILDING. |
| |
| 29) FL ACC CODE 4.1.3(7)(B)THE WIDTH |
| OF DOORS AND OPENINGS SHALL BE NOT LESS |
| THAN 32" CLEAR. |
| |
| 30) FL ACC CODE 4.13.4AT LEAST ONE |
| LEAF OF THE DOUBLE LEAF ENTRANCE DOOR AT |
| THE HEAD OF THE RAMP SHALL HAVE A CLEAR |
| OPENING OF 32". |
| |
| 31) FL ACC CODE 4.13.8THE DOOR |
| THRESHOLD SHALL NOT EXCEED 1/2" IN |
| HEIGHT, AND HAVE A SLOPED BEVEL IN |
| ACCORDANCE WITH FIGURE 7(D) IF THE |
| THRESHOLD HEIGHT EXCEEDS 1/4". |
| |
| 32) FL ACC CODE 4.13.9DOOR HARDWARE |
| SHALL COMPLY WITH THE REQUIREMENTS |
| |
| 33) FL ACC CODE 4.22.1THE TOILET |
| FACILITY IS REQUIRED BY 4.1.3(11) TO BE |
| ACCESSIBLE.THE TOILET FACILITY SHALL |
| BE ON AN ACCESSIBLE ROUTE, WHICH MEANS |
| THAT THE DOORS/OPENINGS LEADING FROM THE |
| ENTRANCE AREA SHALL HAVE A MINIMUM CLEAR |
| OPENING OF 32" IN ACCORDANCE WITH 4.13.5 |
| |
| 34) FL ACC CODE 4.22.3SUBMIT A PLAN OF |
| THE TOILET TO DEMONSTRATE COMPLIANCE |
| WITH THE CLEAR FLOOR SPACE AND |
| ACCESSIBLE FIXTURES AND CONTROL |
| REQUIREMENTS, AND THE REQUIREMENTS FOR |
| SINKS (FL ACC CODE 4.24) AND |
| HANDRAILS/GRAB BARS (FL ACC CODE 4.26) |
| ** PROPOSALS ACCEPTED UNDER PLUMBING |
| PERMIT #01100590 |
| |
| 35) FL ACC CODE 4.1.3(10)AN ACCESSIBLE |
| DRINKING FOUNTAIN SHALL BE PROVIDED. |
| |
| 36) FL ACC CODE 4.1.5SUBMIT DETAILS TO |
| DEMONSTRATE COMPLIANCE WITH THE |
| FOLLOWING ADDITIONAL TECHNICAL |
| REQUIREMENTS AS APPROPRIATE:4.2SPACE |
| ALLOWANCE AND REACH RANGES, |
| 4.3.6SURFACE TEXTURE OF ACCESSIBLE |
| ROUTES, 4.3.9DOORS ON ACCESSIBLE |
| ROUTES, 4.6.3PARKING SPACES, |
| 4.6.4SIGNAGE AT ACCESSIBLE PARKING |
| SPACES, 4.22TOILET ROOMS, |
| 4.29DETECTABLE WARNINGS, 4.30 SIGNAGE, |
| 7.1BUSINESS AND MERCANTILE. |
| |
| 37) FL ENERGY CODE 101.1.2THE ADDITION |
| SHALL COMPLY WITH FLORIDA ENERGY CODE. |
| |
| 38) FL ENERGY CODE 103.0SUBMIT ENERGY |
| CODE COMPLIANCE FORMS TO DEMONSTRATE |
| COMPLIANCE. |
| |
| |
| END OF REVIEW COMMENTS |