2001-11-28 00:00:00 | DENIED |
| REFERENCE: SPC-94 - FACBC-97 |
| |
| 1) SHT A2.1 PLEASE SUBMIT CALCULATIONS |
| FOR MINIMUM FIXTURES PER SPC TABLE 407. |
| 2) SHT A2.3 PLEASE SUBMIT CALCULATIONS |
| FOR ROOF DRAINAGE, PRIMARY AND SECONDARY |
| DRAINS USING SPC SEC 1108 & 1109. ADD |
| 1/2 THE AREA OF ALL VERTICAL WALLS AND |
| INCLUDE AREA OF UPPER ROOFS DRAINING ON |
| TO ROOF. SHOW LOCATION OF SCUPPERS THAT |
| DRAIN TYPICAL ROOFS AT CORNERS. |
| 3) PLEASE PROVIDE A STORM RISER DIAGRAM |
| WITH ALL SQ FOOTAGE SHOWN AT EACH SECT- |
| ION. |
| 4) SHT A7.1 DETAIL #4 PLEASE SHOW DETAIL |
| OF FACBC SEC 4.18.2 & 4.18.3 FOR URNAL. |
| 5) SHT A7.1 DETAIL #11 PLEASE SHOW DE- |
| TAIL FOR KITCHEN SINK SEC 4.24.2, 4.24.3 |
| AND 4.24.4 FACBC. |
| 5) SHT P0.1 PLUMBING NOTES #13, AIR |
| CHAMBERS TO BE ACCESSIBLE AND RECHARGE- |
| ABLE IF USED. WATER HAMMER ARRESTORS DO |
| NOT NEED ACCESS IF APPROVED TYPE. |
| 6) SHT PO.2 PLEASE PROVIDE A WATER RISER |
| DIAGRAM WITH PIPE SIZES AND SHOW WATER |
| HAMMER ARRESTORS LOCATED CLOSE TO FIX- |
| TURES IN AN "EFFECTIVE RANGE" NOT AT TOP |
| OF DROP. |
| 7) IRRIGATION, LICENSED PLUMBING CONTRAC |
| TOR TO SUPPLY A VALVE, WATTS-N36 VACUUMN |
| BREAKER ABOVE GROUND FOR IRRIGATION FROM |
| POTABLE WATER. |
| |