Plan Review Notes
Plan Review Notes For Permit 01110060
Permit Number 01110060
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-28 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT A2.1 PLEASE SUBMIT CALCULATIONS
 FOR MINIMUM FIXTURES PER SPC TABLE 407.
 2) SHT A2.3 PLEASE SUBMIT CALCULATIONS
 FOR ROOF DRAINAGE, PRIMARY AND SECONDARY
 DRAINS USING SPC SEC 1108 & 1109. ADD
 1/2 THE AREA OF ALL VERTICAL WALLS AND
 INCLUDE AREA OF UPPER ROOFS DRAINING ON
 TO ROOF. SHOW LOCATION OF SCUPPERS THAT
 DRAIN TYPICAL ROOFS AT CORNERS.
 3) PLEASE PROVIDE A STORM RISER DIAGRAM
 WITH ALL SQ FOOTAGE SHOWN AT EACH SECT-
 ION.
 4) SHT A7.1 DETAIL #4 PLEASE SHOW DETAIL
 OF FACBC SEC 4.18.2 & 4.18.3 FOR URNAL.
 5) SHT A7.1 DETAIL #11 PLEASE SHOW DE-
 TAIL FOR KITCHEN SINK SEC 4.24.2, 4.24.3
 AND 4.24.4 FACBC.
 5) SHT P0.1 PLUMBING NOTES #13, AIR
 CHAMBERS TO BE ACCESSIBLE AND RECHARGE-
 ABLE IF USED. WATER HAMMER ARRESTORS DO
 NOT NEED ACCESS IF APPROVED TYPE.
 6) SHT PO.2 PLEASE PROVIDE A WATER RISER
 DIAGRAM WITH PIPE SIZES AND SHOW WATER
 HAMMER ARRESTORS LOCATED CLOSE TO FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF DROP.
 7) IRRIGATION, LICENSED PLUMBING CONTRAC
 TOR TO SUPPLY A VALVE, WATTS-N36 VACUUMN
 BREAKER ABOVE GROUND FOR IRRIGATION FROM
 POTABLE WATER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377