Plan Review Notes
Plan Review Notes For Permit 01110060
Permit Number 01110060
Review Stop M
Sequence Number 1
Notes
Date Text
2001-12-08 00:00:00******************DENIED****************
  
  
 AS PER FIRE DEPT COMMENTS ALL STORAGE &
 ELECTICAL ROOMS ARE TO BE FIRE RATED.
 PLEASE IDENTIFY FIRE DAMPERS ON PLAN.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. (NFPA 90A
 4-4.4.3)
  
 ADDITIONAL PERMIT REQUIRED FOR HOOD AND
 FIRE SUPRESSION.PLEASE PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA/PRODUCT
 APPROVALS WITH PERMIT APPLICATION.
  