Plan Review Notes For Permit 01110060 |
Permit Number |
01110060 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-26 00:00:00 | 1) IT DEPENDS WHEN THE BUILDING IS | | OFFICIALLY PERMITTED WHAT FIRE CODE | | WILL BE USED. ON JANUARY 1, 2002, THE | | FLORIDA FIRE PREVENTION CODE WILL BE | | USED WHICH INVOKES THE 2000 EDITION | | OF THE LIFE SAFETY CODE. | | 2) SINCE NO FIRE SPRINKLER SYSTEM IS | | PLANNED, ALL STORAGE ROOMS, AND | | ELECTRICAL ROOM ARE TO BE FIRE RATED. | | 3) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | FOR HOOD,DUCT,AND EXTINGUISHING SYSTEM | | PLANNED FOR KITCHEN. | | 5) BOARDROOM DOORS MUST SWING IN THE | | DIRECTION OF EXIT TRAVEL. PRELIMINARY | | OCCUPANT LOAD CALCULATIONS INDICATE | | LOADS OF 50 OR MORE PERSONS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT. 8497 | | 835-2910 |
|