Plan Review Notes
Plan Review Notes For Permit 01110060
Permit Number 01110060
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-26 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO BE SHOWN. PLANS HAVE BEEN DONE\\
 WITH CONNECTED LOADS SHOWN IN THE PAST,
 LOAD CALCS ARE REQ`D TO BE SHOWN.
 PER 215-5, 220-3,220-10,220-11,220-13
 PLEASE NOTE THAT ALL CONTINUOUS LOADS
 NEED TO BE SHOWN AT 125% PER 230-42,215-
 3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372