2001-12-18 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| SBC = STANDARD BUILDING CODE |
| SBC*= STANDARD BUILD'G CODE (AMENDMENTS) |
| FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| FL ENERGY CODE = FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| |
| 1) SBC* 104.2.3NONE OF THE THREE SETS |
| OF PLANS SUBMITTED HAVE ALL OF THE |
| ARCHITECTURAL PLANS PROPERLY SEALED.AT |
| LEAST ONE SET OF PLANS SHALL BE SIGNED |
| AND SEALED. |
| |
| 2) SBC 1012.1.2THE BOARD ROOM CAN |
| ACCOMMODATE MORE THAN 50 OCCUPANTS.THE |
| DOORS SHALL OPEN IN THE DIRECTION OF |
| EGRESS. |
| |
| 3) SBC 704.1.3.3.1IF THE WATER HEATER/ |
| BOILER EXCEEDS A HEAT INPUT CAPACITY OF |
| 200 000 BTUH OR A WATER TEMPERATURE OF |
| 210 DEGREES-F OR A NOMINAL WATER |
| CAPACITY OF 120 GALLONS, IT SHALL BE |
| SEPARATED FROM THE REST OF THE BUILDING |
| BY 1-HOUR FIRE-RESISTANT CONSTRUCTION. |
| CONFIRM WHETHER THIS IS APPLICABLE. |
| |
| 4) SBC* 1503.1.3.2THE ABOVE-DECK ROOF |
| INSULATION SHALL BE MECHANICALLY |
| FASTENED. |
| |
| 5) SBC 1503.1.5THE KITCHEN AIR INTAKE |
| DUCT SHALL BE INSTALLED TO LEAVE AT |
| LEAST 18" CLEARANCE FOR ACCESS TO THE |
| ROOF COVERING. |
| |
| 6) SBC 1403.2.1THE DECORATIVE CAST |
| STONE PANELS (SHEET A5.2, DETAIL 1) |
| SHALL BE NOT LESS THAN 1 5/8" THICK AND |
| FIXED IN ACCORDANCE WITH SBC 1403.2.8. |
| |
| 7) SBC* 1804.2.2SHEET S-3. FOUNDATION |
| NOTE 1A REFERS TO A SOIL REPORT BY |
| ARDAMAN AND ASSOCIATES.A SOIL REPORT |
| SHALL BE SUBMITTED. |
| |
| 8) FL ACC CODE 4.6.3THE TWO ACCESSIBLE |
| PARKING SPACES SHALL EACH BE AT LEAST |
| 12' WIDE AND THE COMMON ACCESS AISLE AT |
| LEAST 5' WIDE.WHILST SHEET A1.2 SHOWS |
| ADEQUATE WIDTH, SHEET A1.1 SHOWS AN |
| OVERALL WIDTH LESS THAN THE REQUIRED |
| MINIMUM. |
| |
| |
| END OF REVIEW COMMENTS |