2002-01-18 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS. PRODUCT APPROVAL SUBMITTED IS
 FOR INSTALLATION IN A WOOD FRAME. SEE
 PRODUCT APPROVAL FRONT PAGE.
 -PROVIDE LEGIBLE DRAWINGS ALSO.
 2-TRUSS DRAWINGS:
 NOTE: CONTRACTOR CHANGED TRUSS CO.
 NOW, THERE ARE NEW COMMENTS FOR NEW
 ENGINEERED TRUSS PACKAGE.
 A)ENGINEER TO UPDATE ALL GENERAL TRUSS
 DRAWINGS TO REFLECT ACTUAL CODES:
 SBC 1997 FOR 110 MPH OR ASCE 7-95 FOR
 140 MPH WIND LOAD. REVISE AS REQUIRED.
 B)THERE ARE TWO DIFFERENT ENGINEERS
 SIGNING AND SEALING THESE DRAWINGS.
 FOLLOW THE REQUIREMENTS OF CHAPTER
 471 FOR A CHANGE OF ENGINEER.
 C)GENERAL TRUSS DRAWINGS ARE NOT LEGIBLE
 D)ENGINEERED TRUSSES ARE DESIGNED USING
 ASCE 7-98 FOR 110MPH. IF USING ASCE-98
 THEN, USE THE RIGHT WIND LOAD ZONE,
 WHICH IS 140MPH ZONE. REVISE AS REQ'D.
 E)CLARIFY WHAT IT MEANS ON ENGINEERED
 TRUSS DRAWINGS WHEN REFERING TO 15'
 ABOVE GROUND LEVEL. IS THIS THE MEAN
 ROOF HEIGHT? OR WALL HEIGHT?. SPECIFY
 AS REQUIRED AND REMEMBER THAT THIS
 BUILDING HAS AN SLOPED ROOF, NOT FLAT
 ROOF. REVISE AS REQUIRED.
 3-SEE PLANS FOR ADDITIONAL COMMENTS AND
 REVISE ORIGINAL PLANS TO AVOID DELAYS
 OR UNNECESSARY RETURNS FOR FUTURE
 SUBMITTALS.
  
  
  
 NOTE: THERE WILL BE A RESUBMITTAL FEE
 FOR TRUSS DRAWINGS. THEY HAVE BEEN
 REVIEWED/DENIED TWICE ALREADY.