2001-11-30 00:00:00APPROVED WITH PROVISO:
 1-REVISE THE ENERGY CALCULATIONS:
 -UNDER ATTIC AREA IS INCORRECT. SEE
 SECTION 604.1.A.1 OF FLORIDA ENERGY
 CODE FOR BUILDING CONSTRUCTION, 1997.
 2-PROVIDE CURRENT UL ASSEMBLY # FOR ONE
 HR FIRE RATED GLASS BLOCK ASSEMBLY.
 3-PROVIDE UPDATED PRODUCT APPROVAL FOR
 ENTRY DOORS.
 4-PROVIDE STRUCTURAL HANGING DETAIL FOR
 AHU. SPECIFY ALL CONNECTORS. SECTION
 104.2.2 OF CITY AMENDMENTS TO SBC 1997
 5-REVISE WINDOW SIZE FOR BEDROOM #3.
 24SH WINDOW DOESN'T MEET THE MINIMUM
 CLEAR HEIGHT OPENING OF 24".
 SECTION 1005.4 SBC 1997.
 6-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 SBC 1997.
 7-TRUSS DRAWINGS:
 -UPDATE GENERAL TRUSS DETAILS. USE ASCE
 7-95 FOR 140MPH, NOT ASCE 7-93 FOR 110
 -REVIEW STAMP BY ENGINEER OF RECORD
 DOESN'T IDENTIFY FIRM WHO REVIEWED IT.
 8-SOIL TEST REPORT ENGINEER TO PROVIDE
 ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 9-SEE PLANS FOR ADDITIONAL COMMENTS.
 PLEASE BRING BACK REVIEWED SETS AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW.