2002-01-03 00:00:00SECOND CHECKLIST:
 1-ENERGY CALCULATIONS WERE NOT REVISED.
 UNDER ATTIC AREA IS INCORRECT. SEE SEC
 604.1.A.1 FLORIDA ENERGY CODE, 1997 ED
  
 NOTE:THIS ITEM WAS REQUESTED ON PREVIOUS
 CHECKLIST AND ON OTHER REVIEWS. STILL,
 ENERGY CALCS ARE RESUBMITTED UNCHANGED
  
 2-PROVIDE UPLIFT & GRAVITY CALCULATIONS
 FOR BASE DETAIL AT STEEL COLUMNS.
 ALSO, COMPLETE DETAIL SHOWING COLUMN
 MIN. EMBEDMENT ETC.
 3-CONNECTOR SPECIFIED FOR TRUSS H7B DOES
 NOT RESIST THE UPLIFT LOADS CALCULATED
 ON ENGINEERED TRUSSES.
 ALSO, CLEARLY INDICATE SIZE OF
 CONNECTOR SPECIFIED. EG: THERE ARE
 SEVERAL SIZES OF HETAL CONNECTORS.