2001-12-01 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMENCEMENT.
 2-PROVIDE COMPLETE SECTION/DETAIL AT
 INTERIOR BEARING WALL BETWEEN GARAGE
 AND FOYER SHOWING RECESS AT GARAGE.
 SEE SIZE OF FOOTING SPECIFIED.
 SPECIFY ALL FASTENERS.
 3-REVISE ATTIC ACCESS SIZE AT MASTER
 BEDRM. SEE PLANS & SEC. 2309.6 SBC/97.
 ALSO, REVISE DETAIL D/2.
 4-SPECIFY CONNECTORS AT BOTTOM OF STEEL
 COLUMNS AT REAR PORCH. SEC. 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 5-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS. SEC. 2405.2 SBC 1997.
 6-CLEARLY INDICATE ON PLANS THE OPTIONS
 THAT ARE GOING TO BE BUILT. CROSS OUT
 THE OTHERS.
 7-PROVIDE PRODUCT APPROVAL FOR:
 A)FRENCH DOORS WITH SIDELITES SINGLE
 ASSEMBLY IF OPTION IS SELECTED.
 B)FIXED GLASS AT BREAKFAST AREA. SEE
 SIZE SHOWN ON PLANS.
 C)ENTRY DOORS PRODUCT APPROVAL EXPIRED.
 8-REVISE ENERGY CALCULATIONS:
 -UNDER ATTIC AREA IS INCORRECT. SEE
 SEC. 604.1.A.1 OF FL. ENERGY CODE,1997
 9-CONNECTOR SPECIFIED FOR TRUSS H7B DOES
 NOT RESIST THE UPLIFT LOADS. SEE
 ENGINEERED TRUSSES.
 10-ROOF TRUSSES:
 -UPDATE ALL GENERAL DETAILS. USE ASCE
 7-95 FOR 140MPH, NOT ASCE 7-93. SEE
 COMMENTS ON REVIEWED SET.
 11-SEE PLANS FOR ADDITIONAL COMMENTS AND
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW.