Plan Review Notes
Plan Review Notes For Permit 01101914
Permit Number 01101914
Review Stop R
Sequence Number 2
Notes
Date Text
2002-01-04 00:00:00SECOND CHECKLIST:
 1-ENERGY CALCULATIONS WERE NOT REVISED.
 UNDER ATTIC AREA IS INCORRECT. SEE SEC
 604.1.A.1 FLORIDA ENERGY CODE, 1997 ED
  
 NOTE: THIS ITEM WAS REQUESTED SEVERAL
 TIMES BEFORE AND STILL IS NOT DONE.
  
 2-PROVIDE UPLIFT & GRAVITY CALCULATIONS
 FOR BASE DETAIL AT STEEL COLUMNS.
 ALSO, COMPLETE DETAIL SHOWING COLUMN
 MIN. EMBEDMENT, ETC.
 3-CONNECTOR SPECIFED FOR TRUSS H7B DOES
 NOT RESIST THE UPLIFT LOADS CALCULATED
 ON ENGINEERED TRUSSES.
 ALSO, CLEARLY SPECIFY SIZE OF
 CONNECTOR SPECIFIED. THERE ARE SEVERAL
 SIZES OF HETAL OR HETA CONNECTORS.