Plan Review Notes
Plan Review Notes For Permit 01101914
Permit Number 01101914
Review Stop R
Sequence Number 1
Notes
Date Text
2001-12-03 00:00:00CHECKLIST:
 1-NEED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE SECTION/DETAIL AT
 INTERIOR BEARING WALL BETWEEN GARAGE
 AND FOYER AREA SHOWING THE RECESS AT
 GARAGE SIDE. SEE SIZE OF FOOTING
 SPECIFIED. SPECIFY ALL FASTENERS.
 3-REVISE ATTIC ACCESS SIZE AT MASTER BED
 RM. ALSO, REVISE DETAIL D/2. SEE PLANS
 AND SECTION 2309.6 SBC 1997.
 4-PROVIDE STEEL COLUMN DETAIL SHOWING
 CONNECTORS AT BOTTOM OF COLUMN. SEC.
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 5-PROVIDE PRODUCT APPROVAL FOR:
 A)FRENCH DOORS WITH SIDELITES SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 B)FIXED GLASS AT BREAKFAST AREA WITH
 SIZE SHOWN ON PLANS.
 C)ENTRY DOORS PRODUCT APPROVAL EXPIRED.
 6-REVISE ENERGY CALCULATIONS:
 -UNDER ATTIC AREA IS INCORRECT. SEE SEC
 604.1.A.1 FLORIDA ENERGY CODE, 1997 ED
 7-CONNECTOR SPECIFIED FOR TRUSS H7B DOES
 NOT RESIST THE UPLIFT LOADS CALCULATED
 8-ROOF TRUSSES:
 -UPDATE ALL GENERAL TRUSS DETAILS. USE
 ASCE 7-95 140MPH, NOT ASCE 7-93. SEE
 COMMENTS ON REVIEWED SET.
 9-SEE PLANS FOR ADDITIONAL COMMENTS.
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW.