Plan Review Notes For Permit 01101896 |
Permit Number |
01101896 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-20 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) PAGE 2 0F 2 SHOW 5' TURNING RADIUS IN | | SHOWER BATH AS REQUIRED IN FACBC SEC | | 4.2.3 | | 2) PAGE 2 OF 2, SHOWER STALL. SHOW | | COMPLIANCE WITH FACBC SEC 4.21. SHOW DE- | | TAILS FOR SEC 4.21.1 THRU 4.21.8 | | 3) PAGE 2 0F 2, SHOWER NOT SHOWN ON | | SANITARY RISER DIAGRAM. | | 4) PAGE 2 OF 2, PLUMBING NOTES #14. | | AIR CHAMBERS ARE QUICK FIX AND REQUIRE | | ACCESS PANEL AND VALVES TO RECHARGE PER | | SPC 607.8.3 AND PDI-WH 201. APPROVED | | WATER HAMMER ARRESTORS DO NOT REQUIRE | | ACCESS AND SHALL BE SIZED AND LOCATED | | PER MANUFACTURE INSTALLATION INSTRUCTION | | AND PDI-WH 201. | | 5) PAGE 2 0F 2, 2 COMPARTMENT STAINLESS | | STEEL SINK. PLEASE INDICATE USAGE FOR | | BLDG SO A DETERMINATION CAN BE MADE FOR | | THE DRAINAGE SYSTEM FOR SINK. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|