2001-11-20 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE 2 0F 2 SHOW 5' TURNING RADIUS IN
 SHOWER BATH AS REQUIRED IN FACBC SEC
 4.2.3
 2) PAGE 2 OF 2, SHOWER STALL. SHOW
 COMPLIANCE WITH FACBC SEC 4.21. SHOW DE-
 TAILS FOR SEC 4.21.1 THRU 4.21.8
 3) PAGE 2 0F 2, SHOWER NOT SHOWN ON
 SANITARY RISER DIAGRAM.
 4) PAGE 2 OF 2, PLUMBING NOTES #14.
 AIR CHAMBERS ARE QUICK FIX AND REQUIRE
 ACCESS PANEL AND VALVES TO RECHARGE PER
 SPC 607.8.3 AND PDI-WH 201. APPROVED
 WATER HAMMER ARRESTORS DO NOT REQUIRE
 ACCESS AND SHALL BE SIZED AND LOCATED
 PER MANUFACTURE INSTALLATION INSTRUCTION
 AND PDI-WH 201.
 5) PAGE 2 0F 2, 2 COMPARTMENT STAINLESS
 STEEL SINK. PLEASE INDICATE USAGE FOR
 BLDG SO A DETERMINATION CAN BE MADE FOR
 THE DRAINAGE SYSTEM FOR SINK.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377