Plan Review Notes
Plan Review Notes For Permit 01101896
Permit Number 01101896
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-19 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT
 PER 600-5.
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER NEC. 220-3/220-13/220-11
 PLEASE NOTE ALL CONTINUOUS LOADS AT 125%
  
  
 4)NOTE: PLEASE NOTE THAT RISER SHOW AN
 EQUIPMENT GROUNDING CONDUCTOR BEING
 INSTALLED BETWEEN METERCAN AND PANEL....
 PLEASE NOTE THAT THIS IS ONLY INSTALLED
 AFTER FIRST MEANS OF DISCONNECT.
  
 5)NOTE: PLEASE INDICATE ON PLANS THE
 PANEL AS HAVING A MCB.
  
 6)NOTE: PLEASE CLARFIY 1 CIRCUIT FOR
 LIGHTING AT 1-POLE 15A WITH 2124W`S?
 SEEMS TO EXCEED OCP.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372