Plan Review Notes For Permit 01101896 |
Permit Number |
01101896 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-19 00:00:00 | ***************** UNSAT ************ | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | #`S ON PLANS AND CORRELATE WITH THE | | SUBMITTED PANEL SCHEDULE. | | | | 2)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT | | PER 600-5. | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS | | PER NEC. 220-3/220-13/220-11 | | PLEASE NOTE ALL CONTINUOUS LOADS AT 125% | | | | | | 4)NOTE: PLEASE NOTE THAT RISER SHOW AN | | EQUIPMENT GROUNDING CONDUCTOR BEING | | INSTALLED BETWEEN METERCAN AND PANEL.... | | PLEASE NOTE THAT THIS IS ONLY INSTALLED | | AFTER FIRST MEANS OF DISCONNECT. | | | | 5)NOTE: PLEASE INDICATE ON PLANS THE | | PANEL AS HAVING A MCB. | | | | 6)NOTE: PLEASE CLARFIY 1 CIRCUIT FOR | | LIGHTING AT 1-POLE 15A WITH 2124W`S? | | SEEMS TO EXCEED OCP. | | | | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|