Plan Review Notes For Permit 01101812 |
Permit Number |
01101812 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-11-19 00:00:00 | *************** UNSAT ***************** | | | | 1)NOTE: PLEASE NOTE THAT CIRCUITS FOR | | LIGHTING ON BLDGS "E" AND "F" ARE | | SHOWN COMING FROM OTHER BLDGS. | | PLEASE NOTE MEANS OF DISCONNECT FOR | | THESE CIRCUITS PER 225-31. PLEASE SHOW. | | | | 2)NOTE: PLEASE PROVIDE VOLTAGE DROP FOR | | LIGHTING FIXTURES "TYPE M" SCALE SHOWS | | FIXTURES AT WAY OVER 300`- 400` OF | | CONDUIT AND WIRE. | | | | 3)NOTE: PLEASE PLACE NOTE ON PLANS THAT | | MEANS OF DISCONNECT SHALL BE PROPERLY | | LABELED.225-37 | | | | 4)NOTE: PLEASE NOTE THAT RISER SHOW A | | SINGLE PHASE SERVICE AND YET METER TO | | MAIN PANEL SHOWS A #1 BOND?? PLEASE NOTE | | THAT THIS SHOWN AS PARALLELING THE | | NEUTRAL. | | | | 5)NOTE: PLEASE SHOW MEANS OF GROUNDING | | FOR EACH PANEL AT EACH BUILDING,250-50 | | THIS IS SHOWN FOR PANEL"HP" BUT NOT FOR | | OTHERS. | | | | PLEASE NOTE THAT ALL PANELS AT EACH | | BLDG TO BE LABELED AS TO "MAIN" DISC. | | LOCATION. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|