2001-11-26 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01101812
 1925 S OLIVE AV
 CONT: IRONWOOD PROPERTIES
 TEL: (561) 279-8952
  
 SBC=1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
 FL S. S.= FLORIDA STATE STATUTE
  
 1)- FL S S 514.021 SHOW COMPLIANCE WITH
 FENCING & REQUIRED SECURE ENTRY AROUND
 THE POOL AREA.
  
 2)- THE PERMIT APPLICATION STATES THIS
 APPLICATION WILL BE FOR CABANAS, TRELLIS
 AND WALL, IS THE POOL DECK TO BE CONSID-
 ERED UNDER THIS PERMIT? IF SO THE PLANS
 NEED TO SHOW THE SLOPE AWAY FROM THE
 POOL, NOTE THE WALL ON THE BACK SIDE OF
 THE TRELLIS WILL NOT ALLOW FOR DRAIAGE?
  
 3)- SHEET A.63 DOESN'T HAVE ANY SECTIONS
 THROUGH THE CABANA SLABS, INDICATING THE
 FOUNDATION DESIGN, SOILS TERMITE TREAT-
 MENT OR VAPOR BARRIER. THERE IS NO INFOR
 MATION ON THE VERTICLAL NOR HORIZONTAL
 STEEL REINFORCING OR COLUMN BEAM DESIGN.
  
 4)- SBC 104.2.2* DISCREPANCY BETWEEN
 SHEETS A.62 & E.8/P.1 SEE STORAGE LAYOUT
  
 5)- PLUMBING DETAILS VENTING WILL RE-
 QUIRE 3" VENTS FOR EACH CABANA. THE DE-
 TAILS FOR THE BEAM ARE NOT INDICATED FOR
 THESE 2 BUILDINGS, IF CONCRETE BEAM SBC
 1907.3.5(1) PIPES EMBEDDED IN BEAMS
 SHALL NOT BE LARGER IN OUTSIDE DIMENSION
 THAN 1/3 THE OVERALL THICKNESS OF THE
 BEAM.
 IF BLOCK, A MASONRY APPLICATION,
 ACI530.(4.1.1.1) DESIGN SHALL NOT CONSID
 ER CONDUITS,PIPES OR SLEEVES AS
 STRUCURALLYREPLACING THE DISPLACED
 MASONARY.
  
 6)- SBC 1204.2 PUBLIC RESTROOMS, THE
 WALLS & FLOORS OF ALL PUBLIC RESTROOMS
 SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4 FT ABOVE THE
 FLOOR LINE.
  
 7)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 ALL GLAZED OPENINGS WILL REQUIRE PRODUCT
 TESTING, WINDOWS, DOORS & ROOFING ASSEM-
 BLIES.
  
 8)- SHEET A.62 BAR-B-Q GRILL, THERE
 ISN'T ACCESS TO THE BAR-B-Q GRILL AS
 REQUIRED UNDER THE FAIR HOUSING ACT.
 SEE 4.3 ACCESSIBLE ROUTE, & 4.5 GROUND
 AND FLOOR SURFACES.
  
 9)- SHEET A.64 DETAIL FOR HI RIB LATH,
 SBC2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM 1063 C. ATTACHMENT OF HI-RIB METAL
 LATH TO HORIZONTAL FRAMING MEMBERS SHALL
 HAVE 1 3/4" PENETRATION INTO HORIZONTAL
 WOOD SUPPORTS.RIB LATH SHALL BE ATTACHED
 AT EACH RIB.
  
 PLANS SHALL BE TAKEN TO PALM BEACH
 COUNTY FOR IMPACT FEE ASSESSMENT.
  
 SBC 104.2.2 ADDITIONAL INFORMATION,
 THERE ARE STAIR DETAILS ON SHEET A.63 &
 S4.0 WHERE ARE THEY TO BE USED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412