Plan Review Notes For Permit 01101800
Permit Number 01101800
Review Stop R
Sequence Number 1
Notes
Date Text
2001-11-16 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL WINDOW MULLIONS
 - FRENCH DOOR
  
 3) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS OR INDICATE
 THAT YOU WILL APPLY UNDER A SEPARATE
 PERMIT.
  
 4) PROVIDE INFORMATION TO INDICATE
 THAT THE ADDITION TO 735 PALM ST.AND THE
 EXISTING STRUCTURE AT 731 PALM ST. WILL
 COMPLY WITH TABLE 600 FOR THE PERCENT OF
 WALL OPENINGS PERMITTED BASED ON THE
 DISTANCE FROM THE PROPERTY LINE OR THE
 ASSUMED PROPERTY LINE BETWEEN TWO
 BUILDINGS ON THE SAME LOT. 97 SBC TABLE
 600 & SEC.504
  
 5) INDICATE ACCESS TO ATTIC TO BE A
 MINIMUM OF 22 X 36 INCHES. SBC 2309.6
  
 6) PROVIDE ONE FOUNDATION VENT OPENING
 WITHIN 3 FT OF EACH CORNER. SBC 1804.6.2
  
 7) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 8) THE ROOF SHEATHING NAILING NOTE UNDER
 THE FLOOR FRAMING NOTES ON SHEET 1 IS
 NOT IN COMPLIANCE WITH GABLE END NAILING
 REQUIREMENTS FOR ZONE 3 PER CITY OF WPB
 AMENDMENTS TO 97 SBC.
  
 9) INDICATE THE METHOD OF ATTACHMENT AND
 FASTENERS THAT WILL BE USED TO CONNECT
 THE WALLS, FOOTING, ETC. OF THE NEW
 ADDITION TO THE EXISTING STRUCTURE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202