Plan Review Notes
Plan Review Notes For Permit 01101674
Permit Number 01101674
Review Stop E
Sequence Number 3
Notes
Date Text
2001-11-28 00:00:00*************** UNSAT *****************
  
 1)NOTE: NOTE, THE LOAD CALCULATIONS
 THAT WERE SUBMITTED DO NOT MEET NEC.
 PLEASE NOTE THAT THE ORIG LOAD SUBMITTED
 WAS ALMOST 200AMPS AND NOW THE NEW
 LOAD CALCS SUBMITTED ARE MISSING MANY
 LOADS THAT ARE REQ`D FOR MIN NEC LOAD
 REQUIREMENTS.
  
 PLEASE SUBMIT FOR REVIEW OR HAVE
 ELECTRICAL PERMIT UNDER THIS PRIME
 VOIDED SO THE POOL PERMIT MAY BE ISSUED
 AND ELECTRICAL CONTRACTOR CAN SUBMIT
 ELECTRICAL PLANS AND PERMIT APPLICATION
 SEPARATELY.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372