Plan Review Notes For Permit 01101674 |
Permit Number |
01101674 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-11-19 00:00:00 | ****************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT LOAD THE | | SUBMITTED LOAD CALCULATIONS DO NOT | | SHOW INCLUDING HEAT PUMP? AND THE LOAD | | IS SHOWN AT 196AMPS ON A 200A SERVICE? | | | | 2)NOTE: PLEASE NOTE THAT HEAT PUMP IS | | NOT INCLUDED ON ANY OF THE TWO PANEL | | SCHEDULES THAT WERE SUBMITTED? PLEASE | | NOTE THAT RISER DIAGRAM SHOWS A PANEL | | "I" ALSO? PANEL SCHEDULE FOR POOL SUB- | | -PANEL DOES NOT SHOW HEAT PUMP EITHER. | | | | PLEASE SUBMIT THE INFORMATION REQUESTED | | PLEASE INCLUDE HEAT PUMP. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|