Plan Review Notes
Plan Review Notes For Permit 01101632
Permit Number 01101632
Review Stop M
Sequence Number 1
Notes
Date Text
2001-10-25 00:00:00 
 PIPE SHALL BE TESTED TO 1 1/2 TIMES
 WORKING PRESSURE OR NOT LESS THAN 100
 PSI WIHICHEVER IS GREATER.TEST IS
 ONLY REQUIRED FROM SHUTOFF VALVESNOT
 FOR THE ENTIRE SYSTEM.
  
 NOTE, CONDENSER WATER PIPING SHALL BE
 BRAZED AS PER 1997 SMC TABLE 1205.