Plan Review Notes For Permit 01101632 |
Permit Number |
01101632 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-25 00:00:00 | | | PIPE SHALL BE TESTED TO 1 1/2 TIMES | | WORKING PRESSURE OR NOT LESS THAN 100 | | PSI WIHICHEVER IS GREATER.TEST IS | | ONLY REQUIRED FROM SHUTOFF VALVESNOT | | FOR THE ENTIRE SYSTEM. | | | | NOTE, CONDENSER WATER PIPING SHALL BE | | BRAZED AS PER 1997 SMC TABLE 1205. |
|