2002-03-06 00:00:00TRUSSES DENIED
  
 1) PROVIDE A SIGNED, SEALED AND DATED
 LETTER FROM THE ARCHITECT (OR A REVISED
 ROOF FRAMING PLAN) SPECIFYING THE
 CONNECTORS FOR EACH END OF TRUSS GT5
 (UPLIFT 3480#), FOR THE CENTER BEARING
 POINT (JOINT 16,UPLIFT 2260#) OF GT4 AND
 (JOINT 18 ,UPLIFT 4038#) OF GT1. THESE
 WERE NOT SPECIFIED ON THE PLANS.
  
 2) TRUSSES DESIGNED TO ASCE 7-98 WILL BE
 ACCEPTED BY THE BUILDING DEPARTMENT IF
 THEY ARE ACCOMPANIED BY A SIGNED, SEALED
 AND DATED LETTER FROM THE DESIGNER OF
 RECORD FOR THE STRUCTURE STATING THAT HE
 NOTES THAT THE TRUSS ENGINEERING HAS
 BEEN DESIGNED TO ASCE7-98 CRITERIA AND
 THIS IS ACCEPTABLE TO HIM AND WILL MEET
 THE DESIGN LOAD REQUIREMENTS OF THE
 STRUCTURE.
  
  
 THE FIRST TRUSS RESUB IS FREE A FEE WILL
 BE ACCESSED FOR EACH SUBSEQUENT RESUB.
 SEE ATTACHMENT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW