2002-02-19 00:00:00TRUSSES DENIED
  
 1) THE ACCEPTED WINDLOAD DESIGN CRITERIA
 FOR THE CITY OF WEST PALM BEACH IS THE
 1997 STANDARD BUILDING CODE SECTION 1606
 WITH A 110MPH WINDLOAD OR ASCE 7-95 WITH
 A 140MPH WINDLOAD.(STRUCTURE IS
 PERMITTED UNDER 1997 SBC.) PLEASE CHANGE
 THE DESIGN INFORMATION ON THE TRUSS
 DRAWINGS, COVERSHEET AND LAYOUT TO ONE
 OF THE TWO ACCEPTED DESIGN PARAMETERS
 LISTED ABOVE AND MAKE SURE ALL THREE
 REFERENCE THE SAME WINDLOAD.
  
 2) PROVIDE A SIGNED, SEALED AND DATED
 LETTER FROM THE ARCHITECT OR A REVISED
 TRUSS DRAWING (SHEET 7) TO ADDRESS ITEMS
 3,4 AND 6 OF THE FIRST REVIEW COMMENTS
 FOR TRUSSES GT5, GT4 AND GT1.
  