Plan Review Notes For Permit 01101604 |
Permit Number |
01101604 |
|
Review Stop |
R |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2002-02-19 00:00:00 | TRUSSES DENIED | | | | 1) THE ACCEPTED WINDLOAD DESIGN CRITERIA | | FOR THE CITY OF WEST PALM BEACH IS THE | | 1997 STANDARD BUILDING CODE SECTION 1606 | | WITH A 110MPH WINDLOAD OR ASCE 7-95 WITH | | A 140MPH WINDLOAD.(STRUCTURE IS | | PERMITTED UNDER 1997 SBC.) PLEASE CHANGE | | THE DESIGN INFORMATION ON THE TRUSS | | DRAWINGS, COVERSHEET AND LAYOUT TO ONE | | OF THE TWO ACCEPTED DESIGN PARAMETERS | | LISTED ABOVE AND MAKE SURE ALL THREE | | REFERENCE THE SAME WINDLOAD. | | | | 2) PROVIDE A SIGNED, SEALED AND DATED | | LETTER FROM THE ARCHITECT OR A REVISED | | TRUSS DRAWING (SHEET 7) TO ADDRESS ITEMS | | 3,4 AND 6 OF THE FIRST REVIEW COMMENTS | | FOR TRUSSES GT5, GT4 AND GT1. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL : | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)659-8096 EXT.8202 |
|