2001-12-06 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) THE GLASS BLOCK IN THE MASTER BATH IS |
| LOCATED IN A HAZARDOUS LOCATION AND IS |
| REQUIRED TO HAVE A MINIMUM UNIFORM FACE |
| THICKNESS OF 0.25 INCH PER 97 SBC 2405.2 |
| PLEASE PROVIDE MANUFACTURE'S SPECS. FOR |
| GLASS BLOCK. |
| |
| 3) NOTE: HUGHES AND SEMCO HAVE BEEN |
| PURCHASED BY USP AND SOME OF THE |
| CONNECTORS HAVE BEEN DISCONTINUED AND |
| OTHERS ARE LISTED IN THE USP CATALOG |
| WITH LOWERED CAPACITIES. |
| THE ANCHOR LEGEND ON SHEET 7 (4) STATES |
| (2) SEMCO TAPR 222 STRAPS W/12-10D NAILS |
| EACH STRAP CAPACITY 3900#. |
| THE SEMCO CATALOG LISTS TAPR 222 W/15- |
| 10D NAILS HAVING AN UPLIFT CAPACITY OF |
| 2000# AND THE USP CATALOG LISTS TAPR 222 |
| W/14- 10D NAILS HAVING AN UPLIFT |
| CAPACITY OF 1485# WITH A REDUCTION IN |
| UPLIFT CAPACITY IF STRAPS ARE LOCATED |
| WITHIN 8" OF EACH OTHER. THEREFORE IT |
| WILL BE NECESSARY TO REVISE YOUR ANCHOR |
| SCHEDULE FOR FUTURE SUBMITTALS. |
| |
| 4) THE SITE SPECIFIC PRODUCT APPROVAL |
| FORMS SUBMITTED FOR THE SLIDING GLASS |
| DOORS AND THE SINGLE HUNG WINDOWS ARE |
| REQUIRED TO BE DATED BY AND HAVE THE |
| EMBOSSED SEAL OF THE DESIGNER OF RECORD. |
| |
| 5) PROVIDE SITE SPECIFIC PRODUCT |
| APPROVALS FOR THE FIXED GLASS WINDOWS |
| AND THE MULLIONS IN ADDITION TO THE |
| ENGINEER'S DRAWINGS. |
| SITE SPECIFIC ENGINEERING (PRODUCT |
| APPROVAL) REQUIRES THE WET SIGNATURE, |
| DATE AND EMBOSSED SEAL OF THE ENGINEER |
| CERTIFYING THE PRODUCT AND OF THE DESIGN |
| PROFESSIONAL OF RECORD. |
| |
| 6) PROVIDE SOIL TEST PER SEC. 1804.2.7 |
| OF CITY AMENDMENTS TO 1997 SBC. |
| |
| |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |