Plan Review Notes For Permit 01101599 |
Permit Number |
01101599 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-10-29 00:00:00 | ****************** UNSAT ************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2)NOTE: PLEASE SHOW GROUNDING AT DETACH- | | ED BLDG.250-32 | | PLEASE NOTE MISSING EQUIPMENT GROUNDING | | CONDUCTOR FROM MAIN HOUSE TO COTTAGE. | | 250-122 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|