Plan Review Notes
Plan Review Notes For Permit 01101545
Permit Number 01101545
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-10-29 00:00:001) STAIR PRESSURIZATION TO BE TIED
 INTO BUILDING'S EMERGENCY POWER
 SYSTEM.
 2) THE STAIR PRESSURIZATION SHALL
 PROVIDE 0.05 OF WATER COLUMN IN
 ADDITION TO STACK EFFECT EXPECTED.
 3) STAIR PRESSURIZATION SHALL ACTIVATE
 UPON ACTIVATION OF INITIATING DEVICES
 FOR THE FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910