Plan Review Notes For Permit 01101533 |
Permit Number |
01101533 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-11-26 00:00:00 | ******************DENIED**************** | | | | PLEASE DESIGNATE OUTSIDE AIR DUCT SIZE, | | MATERIAL AND LOCATION ON PLAN. | | | | OUTSIDE AIR CALCULATIONS INDICATE THREE | | EMPLOYEES,NO INDICATION OF NUMBER OF | | PATIENTS. | | | | CLARIFY "DEVELOPER RM"- NO EXHAUST IS | | INDICATED FROM THIS AREA.SHOW | | COMPLIANCE WITH ASHRAE 62-1989 TABLE 2. | | PROVIDE AIR BALANCE SCHEDULE SHOWING | | COMPLIANCE WITH 1997 SMC 501.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|